Permit Number: TC-COM-0626-00970
Parcel: 14118602A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0626-00970
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/10/2026 Site Zoning APPROVED
07/10/2026 Site Engineering NOT REQUIRED
07/13/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/10/2026 Commercial Building REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov
The proposed toilet room appears to be accessed through a kitchen area and opens directly into a kitchen area. Please revise plane to demonstrate compliance with the following provisions of the 2024 IBC
• 2902.3.1 Access.
The route to the public toilet facilities required by Section 2902.3 shall not pass through kitchens, storage rooms or closets.
• 2902.3.2 Prohibited location for toilet facilities.
Toilet facilities shall not open directly into a room used for the preparation of food for service to the public.
Please contact me if you have any questions about the above comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
07/10/2026 Commercial Electrical REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0626-00970 (10023 E OLD VAIL RD Unit:UNIT 103 TUCSON, AZ 85747)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Note or show all conduits passing into or out-of the walk-in freezer/cooler unit, with sealant and expansion joints per NEC 300.7(A) & (B).
2. Provide GFCI protection for all appliances shown in NEC 210.8(D), such as ovens, stoves, cook tops, water cooler/fountains, microwaves, etc.
3. Provide GFCI protection for receptacle on circuit P1-23, NEC 210.8(B)(2).
4. Show all wiring methods in detail for all new or modified branch circuit conductors and feeders. Conductor type and conduit size/type. Note wet use requirements. NEC arts;300 and 408.4.
07/13/2026 Commercial Mechanical REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0626-00970
ADDRESS/PARCEL: 10023 E OLD VAIL RD Unit:UNIT 103 TUCSON, AZ 85747

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov.

COMMENTS:

1. Show that the walk-in cooler and walk-in freezer comply with the construction and efficiency requirements of Sections C403.10.2 and C403.10.2.1, IECC 2018.
07/13/2026 Commercial Plumbing REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0626-00970
ADDRESS/PARCEL: 10023 E OLD VAIL RD Unit:UNIT 103 TUCSON, AZ 85747

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov.

COMMENTS:

1. Please clarify which grease interceptor is being provided. The GB2 interceptor is identified in Keynote 10 on Sheet P2, while the GB-75 interceptor is specified on Sheet P3. Reference: Section 107.2.1, IBC 2024.
2. All code references throughout the plan set shall identify the applicable adopted codes, including the 2024 I-Codes (IBC, IMC, IPC, etc.) and the 2018 IECC, as adopted and amended by the City of Tucson. Reference: Section 107.2.1, IBC 2024.
07/13/2026 Water - PDSD REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0626-00970
ADDRESS/PARCEL: 10023 E OLD VAIL RD Unit:UNIT 103 TUCSON, AZ 85747

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov.

COMMENTS:

1. A backflow prevention assembly shall be installed as close as practicable to the service connection. Any backflow prevention method shall be installed in accordance with the manufacturer's specifications and Tucson Water's standard details for installation. Reference: Chapter XXVII, Article V, Section 27-76, the Tucson Code.
a. Please provide the size of the backflow preventer associated with the water meter, and the total water demand that will be served by the 1” water meter. Reference: Section 107.2.1, IBC 2024.
07/08/2026 Fire New Construction REVIEW COMPLETED
06/26/2026 PDSD Application Completeness Express REVIEW COMPLETED