Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-0626-00963
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/29/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 06/29/2026 | Commercial Plumbing Express | REQUIRES RESUBMIT | 1. Provide the propane requirements for the proposed electrical generator, including the maximum gas demand, the minimum gas supply pressure, and the maximum gas supply pressure. Reference: Section 402.2, IFGC 2024. 2. Provide capacity (water gallons) of the propane storage tank and show how the installation of the propane storage tank complies with the requirements of Section 6104.3, IFC 2024. If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov |
||
| 06/26/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |