Permit Number: TC-COM-0626-00961
Parcel: 109224440

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0626-00961
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/16/2026 Commercial Building Standard APPROVED
07/14/2026 Site Zoning Standard APPROVED
07/15/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
06/26/2026 Site Engineering Standard NOT REQUIRED
07/16/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/15/2026 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0626-00961 (3636 N CRAYCROFT RD TUCSON, AZ 85718)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Where subject to physical damage, conductors, raceways, equipment, and cables shall be protected. Clearly show the location of the new sub-panels 1-4, combiner panel and Gateway panel. Provide protection against damage as necessary. NEC 300.4 Protection Against Physical Damage, NEC110.27(B) Prevent Physical Damage. Verify EV charging equipment is protected from physical damage or provide tire stops or bollards or other means to protect from car impacts.
2. Provide conduit depth per NEC 300.5.
3. Detail how the Line-side tap is being done and show this interconnection does not violate the listing of the exiting 1200A Disconnect Switch, NEC 110.3.
4. Provide Fault Current Analysis and show new equipment, breakers, chargers and panels AIC rating sufficient to withstand the calculated Fault Current. Provide Available Fault Current calculations from TEP transformers to all new equipment, 2023 NEC 110.24, NEC 110.9, 110.10.
5. Show the location of the panels and combiners on the Electrical Plan with clear working space compliance, 2017 NEC 110.26(A). PV modules are grounded and may have exposed live parts, use Condition 2 or 3.
6. Clarify the wire count in wire TAG #s 4, 4A,4T. Each conduit should contain the parallel ungrounded conductors and the grounded conductor and grounding conductor. NEC 310.10, 310.10(G). Must have the same number of conductors in each parallel conduit.

7. Provide structural details and calculations for the attachment of the sub-panels/combiner panel to the structure of the canopy, NEC 110.13, IBC 107.1.
06/30/2026 Fire New Construction Standard REVIEW COMPLETED
06/25/2026 PDSD Application Completeness Express REVIEW COMPLETED