Permit Review Detail
Review Status: In Review
Review Details: COMMERCIAL REVIEW - FULL v.3
Permit Number - TC-COM-0626-00956
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: In Review
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| N/A | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| N/A | Commercial Building Standard | PENDING ASSIGNMENT | |||
| N/A | Site Zoning Standard | PENDING ASSIGNMENT | |||
| 07/14/2026 | Commercial Electrical Standard | REQUIRES RESUBMIT | Commercial Electrical Review TC-COM-0626-00956 (8802 E TANQUE VERDE RD TUCSON, AZ 85749) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC). https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov 1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans, design, and calculations, sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304, 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/checklists/commercial_submittal_requirements_july2023.pdf 2. Remove the unrelated ComCheck pages from the provided plans. The Electrical outdoor lighting sheet must be signed and dated to be valid. |
||
| 07/14/2026 | Outdoor Lighting Standard | REQUIRES RESUBMIT | Outdoor Lighting Review TC-COM-0626-00956 (8802 E TANQUE VERDE RD TUCSON, AZ 85749) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC). https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov 1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans, design, and calculations, sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304, 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/checklists/commercial_submittal_requirements_july2023.pdf 2. Show how the Lamp-Tubes, ‘KT-LED*’ are fully shielded. Per OLC 401.2.1(4), architectural features do not grant full-cutoff status. 3. Show lighting fixture ‘B’, ‘C’ & ‘E’, near the residential property line, meets the requirements of OLC 401.3, for house-side shielding, fixture height, and light trespass. >>> Lighting Fixtures ‘B’, ‘C’ & ‘E’ may require house side shielding to prevent light trespass onto the residential properties or certified by the EOR that they do not need it. 4. Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2. >>> per review, this site is using over 75% of allowable lumens and is using more than 100,000 lumens/acre, and thus requires a special inspection. 5. Provide Outdoor Lighting Special Inspection Certificate with Parts A and B completed. https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate_odl.pdf 6. Specify any exceptions used. |
||
| 07/07/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |