Permit Number: TC-COM-0626-00944
Parcel: 138241660

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0626-00944
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/11/2026 Commercial Building APPROVED
07/09/2026 Site Zoning APPROVED
07/10/2026 Water - PDSD APPROVED
06/26/2026 Site Engineering NOT REQUIRED
07/11/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/09/2026 Commercial Electrical REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0626-00944 (1685 W VALENCIA RD Unit:UNIT 141 TUCSON, AZ 85746)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. A signature and date are required as part of the Registrant Seal (Electrical). Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration states that in addition to signing the seal, the registrant shall include the date the document was signed. The EOR seal is missing the date signed.
2. Show electrical outlets, panels and other penetrations within fire-rated walls with fire ratings. IBC 714. Provide fire rating details and products used for receptacles and other electrical penetrations within the new fire rated walls. NEC Article 300.21
3. Show all wiring methods in detail for all circuit conductors and feeders. Conductor type and conduit size/type. ‘Symbols and Legend’ shows ‘elec conduit’. Be specific or provide approved wiring method options. Note wet use requirements. NEC arts;300 and 408.4.
07/10/2026 Commercial Mechanical REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0626-00944
ADDRESS/PARCEL: 1685 W VALENCIA RD Unit:UNIT 141 TUCSON, AZ 85746

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov.

COMMENTS:

1. Provide a ventilation schedule demonstrating how the mechanical system meets the minimum ventilation requirements for the space. Reference: Section 403, IMC 2024.
07/10/2026 Commercial Plumbing REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0626-00944
ADDRESS/PARCEL: 1685 W VALENCIA RD Unit:UNIT 141 TUCSON, AZ 85746

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov.

COMMENTS:

1. Please verify that the distance from the hot water source to the hot water termination for the lavatory complies with the requirements of Section C404.5, IECC 2018 (e.g., 24” for ½” hot water supply piping).
2. Please specify a metering faucet for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10 seconds. Reference: Section 412.13, IPC 2024, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
07/07/2026 Fire New Construction REVIEW COMPLETED
06/25/2026 PDSD Application Completeness Express REVIEW COMPLETED