Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-COM-0626-00919
Parcel: 140420610

Address:
6880 S TUCSON BL

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0626-00919
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/17/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/17/2026 Commercial Mechanical Express REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0626-00919
ADDRESS/PARCEL: 6880 S TUCSON BL TUCSON, AZ 85756

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. Please provide the specifications for the replacement HVAC unit (e.g. manufacturer, model number, heating/cooling capacity, and efficiency ratings). The replacement unit shall have an efficiency rating that is greater than or equal to the minimum required by the Department of Energy that went into effect on January 1, 2023.

A test and balance report is required to verify that the total supply airflow and the outside airflow are at least equal to that which the previous AC unit provided. Reference: Section C503.4, IECC 2018.
06/17/2026 PDSD Application Completeness Express REVIEW COMPLETED