Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0626-00913
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/13/2026 | Outdoor Lighting Standard | APPROVED | Approval under Master permit TC-COM-0626-00908 | ||
| 07/14/2026 | Water - PDSD Standard | APPROVED | Approval under Master permit TC-COM-0626-00908 | ||
| 07/15/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/02/2026 | Commercial Building Standard | REQUIRES RESUBMIT | Willdan Engineering Phoenix Ryan Greene (480) 489-2463 Ryan.Greene@willdan.com 1. COMMENTS noted on TC-COM-0626-00908 Crystal Hacienda Bldg 1 apply to all buildings (1, 4. 5. 6. and 7) |
||
| 07/02/2026 | Commercial Electrical Standard | REQUIRES RESUBMIT | Willdan Engineering Phoenix Russ Cox (602) 901-3678 rcox@willdan.com 1. This wireway is usually sealed by the utility company and the grounding connection shall be made at an accessible point in each service disconnect per NEC 250.24 with a main bonding jumper sized per NEC 250.28(D)(2) 2. The panel location does not provide compliance with NEC 240.24(B). Please clarify. 3. All lighting shall be calculated as a continuous load at 125% 4. Clearly identify all circuits that supply power to the exit/egress lighting unit equipment at the local distribution panel as required by NEC 700.12(H)(2)(4) 5. All load calculations shall calculate the largest motor at 125% as required by NEC 430 & NEC 440 |
||
| 07/02/2026 | Commercial Mechanical Standard | REQUIRES RESUBMIT | Willdan Engineering Phoenix Tom Paradise 602-980-3887 tparadise@willdan.com 1. Page TS100 (1 of 77) Crystal Hacienda MECHANICAL/PLUMBING COMMENTS noted on TC-COM-0626-00908 Crystal Hacienda Bldg 1 apply to all buildings (1, 4. 5. 6. and 7) See pages A301/P101/P301/MP301 |
||
| 07/02/2026 | Commercial Plumbing Standard | REQUIRES RESUBMIT | Willdan Engineering Phoenix Tom Paradise 602-980-3887 tparadise@willdan.com 1. Page TS100 (1 of 77) Crystal Hacienda MECHANICAL/PLUMBING COMMENTS noted on TC-COM-0626-00908 Crystal Hacienda Bldg 1 apply to all buildings (1, 4. 5. 6. and 7) See pages A301/P101/P301/MP301 |
||
| 07/13/2026 | Fire New Construction Standard | REQUIRES RESUBMIT | Resolve all building comments. Provide response letter. john.vincent@tucsonaz.gov 5203495581 |
||
| 07/15/2026 | Site Engineering Standard | REQUIRES RESUBMIT | Site Engineering Review TC-COM-0626-00913 1742 N ORACLE RD BLDG 7 Permit Summary: Remodel existing structures for retail use (TC-COM-0626-00908 is the Main Permit for the Shared Set) Site Engineering comments are as follows: 1. Because this commercial building permit includes a building expansion, it cannot be approved until the associated development package, TD-DEV-0526-00119, is approved by all reviewers. UDC Article 3.3.3.G.7.a To re-submit, visit the Tucson Development Center Online at: https://tdc-online.tucsonaz.gov/#/home The instructions for resubmittal can be found at: Revisions and Resubmittals Engineering Associate: Ryan Insalaco ryan.insalaco@tucsonaz.gov |
||
| 07/06/2026 | Site Zoning Standard | REQUIRES RESUBMIT | 1. COMMENT: Because Building 7 includes an expansion, final Site Zoning approval of this permit cannot be provided until the related development package (TD-DEV-0526-00119) showing the expansion, is first approved. Contact Fernando Garcia, Lead Planner, Site Zoning at fernando.garcia2@tucsonaz.gov. |
||
| 06/23/2026 | PDSD Application Completeness Express | REVIEW COMPLETED | Main permit TC-COM-0626-00908 is in review. |