Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0626-00911
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/13/2026 | Outdoor Lighting Standard | APPROVED | Approval under Master permit TC-COM-0626-00908 | ||
| 07/15/2026 | Site Engineering Standard | APPROVED | |||
| 07/06/2026 | Site Zoning Standard | APPROVED | |||
| 07/14/2026 | Water - PDSD Standard | APPROVED | Approval under Master permit TC-COM-0626-00908 | ||
| 07/15/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/02/2026 | Commercial Building Standard | REQUIRES RESUBMIT | Willdan Engineering Phoenix Ryan Greene (480) 489-2463 Ryan.Greene@willdan.com 1. COMMENTS noted on TC-COM-0626-00908 Crystal Hacienda Bldg 1 apply to all buildings (1, 4. 5. 6. and 7) |
||
| 07/02/2026 | Commercial Electrical Standard | REQUIRES RESUBMIT | Willdan Engineering Phoenix Russ Cox (602) 901-3678 rcox@willdan.com 1. This wireway is usually sealed by the utility company and the grounding connection shall be made at an accessible point in each service disconnect per NEC 250.24 with a main bonding jumper sized per NEC 250.28(D)(2) 2. The panel location does not provide compliance with NEC 240.24(B). Please clarify. 3. All load calculations shall calculate the largest motor at 125% as required by NEC 430 & NEC 440 4. Clearly identify all circuits that supply power to the exit/egress lighting unit equipment at the local distribution panel as required by NEC 700.12(H)(2)(4) 5. All lighting shall be calculated as a continuous load at 125% |
||
| 07/02/2026 | Commercial Mechanical Standard | REQUIRES RESUBMIT | Willdan Engineering Phoenix Tom Paradise 602-980-3887 tparadise@willdan.com 1. Page TS100 (1 of 77) Crystal Hacienda MECHANICAL/PLUMBING COMMENTS noted on TC-COM-0626-00908 Crystal Hacienda Bldg 1 apply to all buildings (1, 4. 5. 6. and 7) See pages A301/P101/P301/MP301 |
||
| 07/02/2026 | Commercial Plumbing Standard | REQUIRES RESUBMIT | Willdan Engineering Phoenix Tom Paradise 602-980-3887 tparadise@willdan.com 1. Page TS100 (1 of 77) Crystal Hacienda MECHANICAL/PLUMBING COMMENTS noted on TC-COM-0626-00908 Crystal Hacienda Bldg 1 apply to all buildings (1, 4. 5. 6. and 7) See pages A301/P101/P301/MP301 |
||
| 07/13/2026 | Fire New Construction Standard | REQUIRES RESUBMIT | Resolve all building comments. Provide response letter. john.vincent@tucsonaz.gov 5203495581 |
||
| 06/23/2026 | PDSD Application Completeness Express | REVIEW COMPLETED | Main Permit TC-COM-0626-00908 is in review. |