Permit Number: TC-COM-0626-00911
Parcel: 115070750

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0626-00911
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/13/2026 Outdoor Lighting Standard APPROVED Approval under Master permit TC-COM-0626-00908
07/15/2026 Site Engineering Standard APPROVED
07/06/2026 Site Zoning Standard APPROVED
07/14/2026 Water - PDSD Standard APPROVED Approval under Master permit TC-COM-0626-00908
07/15/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/02/2026 Commercial Building Standard REQUIRES RESUBMIT Willdan Engineering Phoenix
Ryan Greene
(480) 489-2463
Ryan.Greene@willdan.com

1. COMMENTS noted on TC-COM-0626-00908 Crystal Hacienda Bldg 1 apply to all buildings (1, 4. 5. 6. and 7)
07/02/2026 Commercial Electrical Standard REQUIRES RESUBMIT Willdan Engineering Phoenix
Russ Cox
(602) 901-3678
rcox@willdan.com

1. This wireway is usually sealed by the utility company and the grounding connection shall be made at an accessible point in each service disconnect per NEC 250.24 with a main bonding jumper sized per NEC 250.28(D)(2)
2. The panel location does not provide compliance with NEC 240.24(B). Please clarify.
3. All load calculations shall calculate the largest motor at 125% as required by NEC 430 & NEC 440
4. Clearly identify all circuits that supply power to the exit/egress lighting unit equipment at the local distribution panel as required by NEC 700.12(H)(2)(4)
5. All lighting shall be calculated as a continuous load at 125%
07/02/2026 Commercial Mechanical Standard REQUIRES RESUBMIT Willdan Engineering Phoenix
Tom Paradise
602-980-3887
tparadise@willdan.com

1. Page TS100 (1 of 77) Crystal Hacienda MECHANICAL/PLUMBING COMMENTS noted on TC-COM-0626-00908 Crystal Hacienda Bldg 1 apply to all buildings (1, 4. 5. 6. and 7) See pages A301/P101/P301/MP301
07/02/2026 Commercial Plumbing Standard REQUIRES RESUBMIT Willdan Engineering Phoenix
Tom Paradise
602-980-3887
tparadise@willdan.com

1. Page TS100 (1 of 77) Crystal Hacienda MECHANICAL/PLUMBING COMMENTS noted on TC-COM-0626-00908 Crystal Hacienda Bldg 1 apply to all buildings (1, 4. 5. 6. and 7) See pages A301/P101/P301/MP301
07/13/2026 Fire New Construction Standard REQUIRES RESUBMIT Resolve all building comments. Provide response letter.
john.vincent@tucsonaz.gov
5203495581
06/23/2026 PDSD Application Completeness Express REVIEW COMPLETED Main Permit TC-COM-0626-00908 is in review.