Permit Number: TC-COM-0626-00910
Parcel: 115070750

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0626-00910
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/13/2026 Outdoor Lighting Standard APPROVED Approval under Master permit TC-COM-0626-00908
07/15/2026 Site Engineering Standard APPROVED
07/06/2026 Site Zoning Standard APPROVED
07/14/2026 Water - PDSD Standard APPROVED Approval under Master permit TC-COM-0626-00908
07/15/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/02/2026 Commercial Building Standard REQUIRES RESUBMIT Willdan Engineering Phoenix
Ryan Greene
(480) 489-2463
Ryan.Greene@willdan.com

1. COMMENTS noted on TC-COM-0626-00908 Crystal Hacienda Bldg 1 apply to all buildings (1, 4. 5. 6. and 7)
07/02/2026 Commercial Electrical Standard REQUIRES RESUBMIT Willdan Engineering Phoenix
Russ Cox
(602) 901-3678
rcox@willdan.com

1. This wireway is usually sealed by the utility company and the grounding connection shall be made at an accessible point in each service disconnect per NEC 250.24 with a main bonding jumper sized per NEC 250.28(D)(2)
2. The panel location does not provide compliance with NEC 240.24(B). Please clarify.
3. All lighting shall be calculated as a continuous load at 125%
4. Clearly identify all circuits that supply power to the exit/egress lighting unit equipment at the local distribution panel as required by NEC 700.12(H)(2)(4)
5. All load calculations shall calculate the largest motor at 125% as required by NEC 430 & NEC 440
07/02/2026 Commercial Mechanical Standard REQUIRES RESUBMIT Willdan Engineering Phoenix
Tom Paradise
602-980-3887
tparadise@willdan.com

Page TS100 (1 of 77) Crystal Hacienda MECHANICAL/PLUMBING COMMENTS noted on TC-COM-0626-00908 Crystal Hacienda Bldg 1 apply to all buildings (1, 4. 5. 6. and 7) See pages A301/P101/P301/MP301
07/02/2026 Commercial Plumbing Standard REQUIRES RESUBMIT Willdan Engineering Phoenix
Tom Paradise
602-980-3887
tparadise@willdan.com

Page TS100 (1 of 77) Crystal Hacienda MECHANICAL/PLUMBING COMMENTS noted on TC-COM-0626-00908 Crystal Hacienda Bldg 1 apply to all buildings (1, 4. 5. 6. and 7) See pages A301/P101/P301/MP301
07/13/2026 Fire New Construction Standard REQUIRES RESUBMIT Resolve all building comments. Provide response letter.
john.vincent@tucsonaz.gov
5203495581
06/23/2026 PDSD Application Completeness Express REVIEW COMPLETED Main permit TC-COM-0626-00908 in review