Permit Number: TC-COM-0626-00897
Parcel: 13734001A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0626-00897
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/13/2026 Commercial Building Standard APPROVED
07/13/2026 Commercial Mechanical Standard APPROVED
07/13/2026 Commercial Plumbing Standard APPROVED
07/13/2026 Water - PDSD Standard APPROVED
07/13/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/10/2026 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0626-00897 (1650 W VALENCIA RD TUCSON, AZ 85746)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov


1. Provide GFCI protection per NEC 210.8(D)(2) for the EWC. Reference sheet E2, outside breakroom.
2. Provide GFCI protection per NEC 210.8(D)(2) for the EWC. Reference sheet E2.2, detail 2.
3. Note or show conduit through the roof has Expansion joints as needed for Raceway exposed to different temperatures, NEC 300.7(A) & (B). REF Sheet RE1, Detail 5.
4. Note or show all conduits passing into or out-of the walk-in fridge unit, with sealant and expansion joints per NEC 300.7(A) & (B). Reference Sheet RE1.1, details 4 & 6 as an example.
5. Provide protection from damage and vehicular impact, call out the correct Civil drawing and detail for the bollard placement for chargers and other equipment. NEC 300.4 Protection Against Physical Damage, NEC110.27(B) Prevent Physical Damage. LOCATE/LABEL THE HANDICAP ACCESSIBLE EV CHARGING STALLS, SHOW THE ACCESSIBLE STRIPED ROUTE.
6. Provide disconnecting means at the location of the charging equipment, or provide a plaque installed on the charging equipment denoting the location of the disconnecting means, NEC 625.43.
7. Verify and correct the Civil Drawing REF sheets as called out in the electrical EV* sheets. Reference sheet EV1, detail 2, new Medium Voltage Transformer pad installation note.
8. Provide Power Management markings and plaque per 2023 NEC 750.30(C)(4) Marking. Reference sheet EV2, New Switchboard MSWB, Load Summery Notes.
The equipment that supplies the branch circuit, feeder, or service shall be field marked with the following information:
(1) Maximum current setting

(2) Date of calculation and setting

(3) Identification of loads and sources associated with the current limiting feature

(4) The following or equivalent wording: "The setting for the EMS current limiting feature shall not be bypassed"
07/10/2026 Outdoor Lighting Standard REQUIRES RESUBMIT Outdoor Lighting Review TC-COM-0626-00897 (1650 W VALENCIA RD TUCSON, AZ 85746)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Provide and note that the under-canopy lighting fixture is full cutoff with maximum color temperature of 3500K. Reference Sheet E1.2, detail 8. OLC 402.1.
06/22/2026 Site Engineering Standard REQUIRES RESUBMIT Permit Activity Number: TC-COM-0626-00897 (1st Review)
Project: Interior Remodel of existing Walmart Supermarket building.
Location: 1650 W VALENCIA RD
Review Date: 6/22/2026
Reviewer: Marco Contreras – Engineering Associate - Site Engineering
Reviewer Contact: Marco.contreras@tucsonaz.gov
Related cases:

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed to ensure final approval from Site Engineering.
To help speed up your resubmittal and facilitate shorter review timelines, please include a response letter along with your updated plans and any supporting calculations. In your response letter, address each comment individually and explain what changes were made and where they can be found in the plans. Please do not mark or highlight changes in the drawings at this stage — revision markups are only used after a permit has been issued. Submit your response letter and updated plan set as two separate files.
Site Engineering Review Comments:
1. The proposed new sidewalks, pedestrian pathway connections, and all other exterior modifications proposed at this commercial site will require the submission of a Development Package (Site plan) in accordance with UDC §7.4.3.E. Per UDC §3.3.3.G.2.c, A Development Package (DP) meeting the requirements of the Checklist for Minor Changes to Commercial/Industrial Sites is required to be submitted and approved. The DP is a separate submittal from the building plans. The checklist can be found at: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/minor_changes_to_commercial_industrial_sites_.pdfPlease coordinate through email to confirm any additional studies required based on site conditions & reviewer comments. Note that the Development Package is a separate permit submittal, and must be processed independently of, the building plans.
2. Site Engineering is unable to fully review and approve permit TC-COM-0626-00897 until the associated Development Package is reviewed and approved by all reviewers.
07/09/2026 Site Zoning Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM: Krista Hansen
Planning & Development Services Department – Zoning Review Section

PROJECT: TC-COM-0626-00897
1650 W VALENCIA RD
Walmart Renovations (1st Review)

TRANSMITTAL DATE: 7/9/2026


This site is zoned C-2 (UDC Section 4.7.21).


Comments: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed.

01. COMMENT 1: This project proposes new customer-facing EV charging stations, sidewalks, and crosswalks/pedestrian refuge areas. Per UDC Article 3.3.3.G.2.c., a Development Package (DP) is required when a project proposes, “a reconfiguration of an area outside a building.” A DP, that meets the requirements of Administrative Manual (AM) 2-06, must be submitted and approved prior to approval of this building plan. The Administrative Manual can be found at: https://codelibrary.amlegal.com/codes/tucson/latest/tucson_az_udc/0-0-0-8753


For questions regarding Zoning comments, please contact me at: Krista.Hansen@tucsonaz.gov
06/23/2026 Fire New Construction Standard REVIEW COMPLETED
06/18/2026 PDSD Application Completeness Express REVIEW COMPLETED