Permit Number: TC-COM-0626-00895
Parcel: 12306022C

Address:
1634 N OLSEN AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0626-00895
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/12/2026 Commercial Building Standard APPROVED
07/13/2026 Commercial Mechanical Standard APPROVED
07/13/2026 Commercial Plumbing Standard APPROVED
07/09/2026 Site Zoning Standard APPROVED Ref: TZ-CMP-0526-00088
07/13/2026 Water - PDSD Standard APPROVED
06/18/2026 Site Engineering Standard NOT REQUIRED
07/13/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/09/2026 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0626-00895 (1634 N OLSEN AV TUCSON, AZ 85719)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. The provided Fault Current Analysis shows the short circuit at panel ‘A’ at 12,641A, but the AIC rating for panel ‘A’ is only shown at 10,000A. Provide a panel with an AIC rating sufficient to withstand the calculated Fault Current. 2023 NEC 110.24, NEC 110.9, 110.10, 240.86.
2. Provided GFCI protection for all new and existing receptacles within the new Men’s and Women’s Locker rooms, NEC 210.8(B)(9).
3. Provide the correct circuit designation for a (N) receptacle in the bathroom just off the Vestibule, room 127. Also needs to be show as GFCI protected. NEC 210.8(B)(1). circuit designation currently shows ‘C’-XX. EF-3 is in this same bathroom for reference.
4. Show the existing receptacles withing the Lounge 01, 125, with GFCI protection with the new Jacuzzi/cold plunge. NEC 210.8(B)(8)
5. Multiple receptacles are marked with the incorrect abbreviation, GRCI. Correct and show as GFCI protected.
6. Clarify if the lighting fixtures labeled with ‘LT*’ are existing or new. Are they just being recircuited per the Keyed Notes on sheet E3.0?
07/09/2026 Outdoor Lighting Standard REQUIRES RESUBMIT Outdoor Lighting Review TC-COM-0626-00895 (1634 N OLSEN AV TUCSON, AZ 85719)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Clarify if there are changes to the outdoor lighting. Specifically if LT-11 is new lighting fixtures. Compliance with the outdoor lighting will be required for any new or modified outdoor lighting.
06/22/2026 Fire New Construction Standard REVIEW COMPLETED
06/18/2026 PDSD Application Completeness Express REVIEW COMPLETED