Permit Number: TC-COM-0626-00891
Parcel: 14029008C

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0626-00891
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/10/2026 Commercial Building Standard APPROVED
07/09/2026 Commercial Electrical Standard APPROVED Approved with comments added to plans: see sheet E2.1.
1. Reference sheet E2.1.
a. Circuit B-7 to the EWC, provide GFCI protection per NEC 210.8(D)(2).
Readily accessible per NEC 210.8.
b. Circuit B-24 in the Janitor’s closet, room 122, provide GFCI protection per NEC 210.8(B)(7) & (8).
07/13/2026 Commercial Mechanical Standard APPROVED
07/09/2026 Site Zoning Standard APPROVED
07/13/2026 Water - PDSD Standard APPROVED
07/09/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
06/18/2026 Site Engineering Standard NOT REQUIRED
07/13/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/13/2026 Commercial Plumbing Standard REQUIRES RESUBMIT 1. Provide a minimum of two drinking fountains; one accessible for standing persons and one accessible for persons confined to a wheelchair. Reference: Section 410.3.1, IPC 2024 (see also exception 1,Section 410.3 and Section 410.4, IPC 2024, as amended by the City of Tucson).
2. Provide tempered water for the lavatories with a device conforming to ASSE 1070. Reference: Section 419.5, IPC 2024.
3. Provide metering faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10 seconds for accessibility. Reference: Section 604.4, IPC 2024 and Section 606.4, ICC/ANSI A117.1-09.
4. Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5.1, IECC 2024.

If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
06/22/2026 Fire New Construction Standard REVIEW COMPLETED
06/18/2026 PDSD Application Completeness Express REVIEW COMPLETED