Permit Number: TC-COM-0626-00890
Parcel: 117121930

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0626-00890
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/09/2026 Commercial Electrical Standard APPROVED
07/13/2026 Commercial Mechanical Standard APPROVED
07/09/2026 Site Zoning Standard APPROVED
07/13/2026 Water - PDSD Standard APPROVED
07/13/2026 Commercial Plumbing Standard NOT REQUIRED
06/29/2026 Design Review Standard NOT REQUIRED Proposed improvements are in the interior of the building only.
07/09/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
06/18/2026 Site Engineering Standard NOT REQUIRED
07/13/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/10/2026 Commercial Building Standard REQUIRES RESUBMIT TC-COM-0626-00890 40 E CONGRESS ST
TI: Interior only changes to existing tenant space
Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov
1. Provide the signed and sealed structural calculations, prepared by an Arizona licensed registrant, used in the design of this project. IBC 107.2.7
2. Please provide the City of Tucson Special Inspection Certificate(s) with Parts A and B
completed with the next submittal. IBC 107.1 SI form link:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate.pdf
3. Sheet s1.0/Detail3: Please indicate the type, size, and length of the fasteners to be used for the beam-to-existing column connection. Additionally, provide the required hole diameter and embedment depth (or hole depth) for the connection to demonstrate proper installation and code compliance. IBC 107.2.7
4. Sheet g1.0: Please provide a detailed description of the proposed work within the scope of this permit on the cover sheet. The description should clearly identify the nature and extent of the work being performed so that compliance with the applicable code requirements can be determined. IBC Section 105.3.

Please contact me if you have any questions about the above comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
06/25/2026 Fire New Construction Standard REVIEW COMPLETED
06/18/2026 PDSD Application Completeness Express REVIEW COMPLETED