Permit Number: TC-COM-0626-00887
Parcel: 12106008A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.3

Permit Number - TC-COM-0626-00887
Review Name: COMMERCIAL REVIEW - LIMITED v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/22/2026 Commercial Plumbing APPROVED
09/22/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/22/2026 Commercial Mechanical REQUIRES RESUBMIT Comment not resolved. On M201, the exhaust fan is to, “Switch with light”; while the lighting keynote #2, on E101 calls for the fan to be controlled by an occupancy sensor. The fan should run continuously during the hours of operation. [Initial comment: Provide information on the sequence of operation for the restroom exhaust fan to show that all of the air supplied to the restroom will be exhausted during the hours of operation. Reference: Footnote g, Table 403.3.1.1, IMC 2024.]