Review Date Reviewer's Name Type of Review Description Status Comments
07/01/2026 Commercial Electrical Standard APPROVED
06/18/2026 Site Engineering Standard NOT REQUIRED
N/A Bldg Permits - Post Review Express PENDING ASSIGNMENT
N/A Outdoor Lighting Standard PENDING ASSIGNMENT
N/A Site Zoning Standard PENDING ASSIGNMENT
07/01/2026 Water - PDSD Standard PENDING ASSIGNMENT
07/01/2026 Commercial Building Standard REQUIRES RESUBMIT Willdan Engineering Phoenix
Ed Kulik
ekulik@willdan.com
1. Sheet C1 Provide a site plan showing accessible path of travel to parking and the public way.
2. Sheet A1.0 Provide protrusion protection at drinking fountains or place in alcove. ICCA117
3. Sheet A1.0 Show wall and ceiling rating for storage under stairs.
4. Sheet A1.0 Provide details on installing new openings for windows. Show exterior wall details for repairing exterior wall, Provide manufactures cut sheet for windows.
5. Sheet A1.1 Provide details and calculations for new Guard at stair well.
6. Sheet A3.0 Show Accessible access to break station Sink.
07/01/2026 Commercial Mechanical Standard REQUIRES RESUBMIT 1. Sheet M4 Provide documentation that the mechanical system meets or exceeds the 2018 IECC.
07/01/2026 Commercial Plumbing Standard REQUIRES RESUBMIT 1. Sheet P4 Install Studor Vent per manufactures listing.
06/22/2026 Fire New Construction Standard REVIEW COMPLETED
06/18/2026 PDSD Application Completeness Express REVIEW COMPLETED