Permit Number: TC-COM-0626-00870
Parcel: 13734001E

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0626-00870
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/29/2026 Commercial Building APPROVED
07/01/2026 Commercial Plumbing APPROVED
07/01/2026 Site Zoning APPROVED
07/01/2026 Water - PDSD APPROVED
06/18/2026 Site Engineering NOT REQUIRED
07/01/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/23/2026 Commercial Electrical REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0626-00870 (1710 W VALENCIA RD Unit:UNIT 120 TUCSON, AZ 85746)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov


1. Provide a complete set of electrical drawing for the scope of work being done.
Plans shall include (as necessary for scope of work), but may not be limited to items below:
2. Show all wiring methods in detail for all new or modified branch circuit conductors and feeders. Conductor type and conduit size/type. Note wet use requirements. NEC arts;300 and 408.4. Make clear which circuits are being used for new equipment and which are being remaining the same.
3. Provide a panel schedules, showing the circuits that are being modified, added or removed or existing. NEC arts;300 and 408.4. Include panel bus rating and A.I.C. rating. IBC 107.1. highlight the modified, or new circuits.
4. Provide an electrical plan and Designate the circuit number on the electrical plans, that corresponds to the panel schedule, at the location of each existing, new or modified light fixture, receptacle, and equipment disconnect switch, NEC arts;300 and 408.4. IBC 107.1.
5. Show GFCI protection for any new, modified or reused circuits within the kitchen, NEC 210.8(B) & (D).
07/01/2026 Commercial Mechanical REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0626-00870
ADDRESS/PARCEL: 1710 W VALENCIA RD Unit:UNIT 120 TUCSON, AZ 85746

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. Provide a ventilation schedule demonstrating how the mechanical system meets the minimum ventilation requirements for the space. Reference: Section 403, 2024 IMC.
2. Provide the air balancing data for the air distribution systems served by RTU-1 and RTU-2. Label the design supply and return air quantities (CFM) for the existing diffusers and grilles on the mechanical plans. Reference: Section 608.1, 2024 IMC.
06/21/2026 Fire New Construction REVIEW COMPLETED
06/16/2026 PDSD Application Completeness Express REVIEW COMPLETED