Permit Number: TC-COM-0626-00864
Parcel: 12412121A

Address:
1014 E 12TH ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0626-00864
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/11/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/11/2026 Addressing Validation REQUIRES RESUBMIT If you have questions regarding this review, please contact CDRC@tucsonaz.gov.
Please include the address for all four unit numbers and resubmit after all reviews are complete.
06/11/2026 Commercial Electrical Express REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0626-00864 (1014 E 12TH ST TUCSON, AZ 85719)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. The upgrade of the existing service equipment requires the submission of a basic riser-diagram.
2. Provide an electrical riser diagram, NEC 230.9.
a. Show each meter and address/unit associated with each meter.
b. Show bus bar rating and AIC ratings of the new equipment.
c. Show conductor size and type on the line diagram.
d. Notate the grounding and bonding method, including water line bonding, NEC 250.20(B), 250.24, 250.30(A)(1). Metallic gas lines must be bonded and not be used as the primary grounding method, NEC 250.50, 250.52(B)(1).
06/11/2026 PDSD Application Completeness Express REVIEW COMPLETED