Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2
Permit Number - TC-COM-0626-00846
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/18/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 06/18/2026 | Commercial Electrical Express | REQUIRES RESUBMIT | Commercial Electrical Review TC-COM-0626-00846 (7812 E SPEEDWAY BL TUCSON, AZ 85710) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC). https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov 1. The repair of the existing service equipment requires the submission of a basic riser-diagram. 2. Provide an electrical riser diagram, NEC 230.9. a. Show each meter and address/unit associated with each meter. b. Show bus bar rating and AIC ratings of the new equipment. c. Highlight the parts, conductors, equipment, etc, being repaired. Provide sizing and other info as needed to verify code compliance. |
||
| 06/18/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |