Permit Number: TC-COM-0626-00845
Parcel: 12112415A

Address:
5410 E PIMA ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0626-00845
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/24/2026 Commercial Electrical Standard NOT REQUIRED No electrical work.
06/23/2026 Fire New Construction Standard NOT REQUIRED
06/24/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
06/12/2026 Site Engineering Standard NOT REQUIRED
07/01/2026 Site Zoning Standard NOT REQUIRED
07/01/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/30/2026 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov
1. The submitted plans indicate that the existing damaged masonry wall supporting the masonry wall above is to be removed and the supporting masonry wall is to be replaced with wood posts. Please provide complete structural design, drawings, details, and calculations prepared by the registered design professional demonstrating that the proposed wood post system is capable of supporting all applicable dead, live, wind, and seismic loads previously carried by the masonry wall.
Revise the plans to clearly identify:
A. The size, species, grade, and spacing of the proposed wood posts.
B. The size and material of all beams, headers, and other framing members supporting the wall above.
C. Complete footing and foundation details, including dimensions, reinforcement, and bearing capacity.
D. Post-to-beam and post-to-foundation connection details, including all required connectors and fasteners.
E. Details showing how gravity and lateral loads are transferred into the existing structure.
F. Temporary shoring and sequencing, if required to safely remove the existing load-bearing wall.

Provide sufficient details to demonstrate compliance with the applicable structural provisions of the 2024 IBC. The construction documents shall clearly indicate the nature and extent of the work and include all information necessary to verify code compliance. IBC Sections 107.2.1 and 107.2.1.1.
Please contact me if you have any questions about the above comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
06/11/2026 PDSD Application Completeness Express REVIEW COMPLETED