Permit Number: TC-COM-0626-00817
Parcel: 132166160

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.6

Permit Number - TC-COM-0626-00817
Review Name: COMMERCIAL REVIEW - FULL v.6
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/14/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/14/2026 Commercial Building Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0626-00817
ADDRESS/PARCEL: (845 E OHIO ST Unit:UNIT 109 TUCSON, AZ 85714)
TC-COM-0526-00787 (3002 E GRANT RD Unit:UNIT 2 TUCSON, AZ 85716)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.

Should you have any questions about these Commercial Building comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976.

COMMENTS:
1. OCCUPANT LOAD
a. 2,000 sf is used for Packaging work/activity.
i. Please use 150 sf per person in calculating the occupant load.
ii. With the above in mind 2,000 / 150 = 13.33 occupants.
b. 3,000 sf is left as storage.
i. Please correct this occupant load calculation.
ii. With this in mind 3,000 / 300 = 10.00 occupants.
c. Therefore the sub-total occupant load should be 13.33 + 10.00 = 24
d. The occupant load for the remaining Unit 111 is not known, please indicate this on the drawings.
e. The original Unit 109 space drawings shows 70 occupants.
f. This gives the total-total occupant load for Unit 109 as 94 (24 + 70).
g. Please correct this on Sheet G1.0 Project Data
2. RESTROOM LOCATION
a. Show on the plan drawing(s) the location of the Restrooms.
b. Existing drawings indicate that Hamilton operates in Unit 107 with their own 2 restrooms (please show this on the drawings).
c. WYLD occupies Unit 109 with its own 2 restrooms (please show this on the drawings).
d. Expansion is located in Unit 111 with the assumption that it uses the WYLD Unit 109 restrooms.
e. The balance of Unit 111 area is not clear. Does this unit have restrooms? If so, please show it in the drawings. If it does not have restrooms, does it share the 2 restrooms in Unit 109?
f. Please provide the calculation for the required minimum plumbing fixture for the combined Unit 109 and the rest of Unit 111 spaces to make sure there is enough restrooms.
3. Please resubmit.
09/11/2026 Commercial Mechanical Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0626-00817
ADDRESS/PARCEL: 845 E OHIO ST Unit:UNIT 109 TUCSON, AZ 85714

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov.

COMMENTS:

1. Section 408.2.1.2 requires a minimum continuous air recirculation rate of 1 CFM/sqft and requires the recirculated air to be provided with a minimum MERV 8 filter and a chemical-absorbing filter. The HUSQVARNA Model A1200 air scrubber appears to provide only 1,200 CFM of recirculation, while the 5,000 sqft storage/packing space would require a minimum of 5,000 CFM. Additionally, the listed unit does not appear to be provided with a chemical-absorbing filter. Please clarify how the required recirculation rate and filtration requirements will be met. Reference: Section 408.2.1.2, IMC 2024, as amended by the City of Tucson.
2. Also, Section 408.2.1.1 requires the space to provide mechanical exhaust at 0.2 CFM/sqft. The plans do not indicate an exhaust system serving this space. Please provide the required exhaust and identify the exhaust airflow rate and discharge location. Reference: Section 408.2.1.1, IMC 2024, as amended by the City of Tucson.
08/31/2026 PDSD Application Completeness Express REVIEW COMPLETED