| 07/28/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/28/2026 | Commercial Mechanical Standard | REQUIRES RESUBMIT | No ventilation information submitted. [Initial comment: Please provide an outdoor air ventilation schedule that shows how the mechanical system meets the minimum outdoor air ventilation requirements for the packaging/storage room. Reference: Section 403.3.1.1, IMC 2024.] Note: Include a complete plan set with each submittal. If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov. |
||