Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-COM-0626-00817
Parcel: 132166160

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.5

Permit Number - TC-COM-0626-00817
Review Name: COMMERCIAL REVIEW - FULL v.5
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/20/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/20/2026 Commercial Mechanical Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0626-00817
ADDRESS/PARCEL: 845 E OHIO ST Unit:UNIT 109 TUCSON, AZ 85714

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov.

COMMENTS:

1. Please clarify the proposed activities within the new packaging/storage area. The space ventilation analysis only accounts for one occupant and is classifying the entire zone as storage when it appears to be used as both storage and packaging. Workrooms in Table 403.3.1.1 have different requirements. Please clarify and revise the outside air calculations to reflect the correct occupancy classification. Reference: Section 403.3.1.1, IMC 2024.
2. Also, please demonstrate that this area complies with the exhaust and ventilation requirements of Section 408.2, Marijuana Related Occupancies. Reference: Section 408.2, IMC 2024, as amended by the City of Tucson.
08/07/2026 PDSD Application Completeness Express REVIEW COMPLETED