Permit Number: TC-COM-0626-00817
Parcel: 132166160

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0626-00817
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/29/2026 Commercial Building Standard APPROVED
06/23/2026 Commercial Electrical Standard APPROVED
07/01/2026 Site Zoning Standard APPROVED
06/30/2026 Commercial Plumbing Standard NOT REQUIRED
06/22/2026 Outdoor Lighting Standard NOT REQUIRED No changes to the outdoor lighting.
06/30/2026 Site Engineering Standard NOT REQUIRED
06/30/2026 Water - PDSD Standard NOT REQUIRED
07/01/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/30/2026 Commercial Mechanical Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0626-00817
ADDRESS/PARCEL: 845 E OHIO ST Unit:UNIT 109 TUCSON, AZ 8571

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. Please provide an outdoor air ventilation schedule that shows how the mechanical system meets the minimum outdoor air ventilation requirements for the packaging/storage room. Reference: Section 403.3.1.1, IMC 2024.
2. Provide heating and cooling load calculations to justify the heating/cooling capacity of the HVAC Equipment. Reference: Section C403.1.1 and C502.2.3, IECC 2018.
06/22/2026 Fire New Construction Standard REVIEW COMPLETED
06/09/2026 PDSD Application Completeness Express REVIEW COMPLETED