Permit Number: TC-COM-0625-01285
Parcel: 134234150

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0625-01285
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/25/2025 Site Zoning Standard APPROVED
07/28/2025 Water - PDSD Standard APPROVED
07/17/2025 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
07/09/2025 Site Engineering Standard NOT REQUIRED
07/28/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/24/2025 Commercial Building Standard REQUIRES RESUBMIT July 11, 2025
1st Review

Intertech Architectural Interiors
Attn: Maria Oldham
6089 E. Grant Road
Tucson, Arizona 85712

Re: QUALITY OF LIFE MEDICAL AND RESEARCH CENTER
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0625-01285
Stantec Project Number: 185215066
Stantec File Number: TUC-25-075

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B V-B 10,950 73 Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

1. The individual space square footage and the building area square footage are conflicting. The actual building area indicates 10,500 square feet while the individual space area is indicated as 10,950 square feet.

STRUCTURAL COMMENTS

There are no comments.


MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

General

1. The electrical sheets are missing the fire riser room. Please revise the plans to include this room and the required illumination. [Ref. IBC 2018 Sec. 902.1.4]

2. Please indicate an exit sign in the area of door 101B that clearly indicates the direction of egress travel through that door. [Ref. IBC 2018 Sec.1013.1]


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
07/24/2025 Commercial Electrical Standard REQUIRES RESUBMIT July 11, 2025
1st Review

Intertech Architectural Interiors
Attn: Maria Oldham
6089 E. Grant Road
Tucson, Arizona 85712

Re: QUALITY OF LIFE MEDICAL AND RESEARCH CENTER
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0625-01285
Stantec Project Number: 185215066
Stantec File Number: TUC-25-075

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B V-B 10,950 73 Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

1. The individual space square footage and the building area square footage are conflicting. The actual building area indicates 10,500 square feet while the individual space area is indicated as 10,950 square feet.

STRUCTURAL COMMENTS

There are no comments.


MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

General

1. The electrical sheets are missing the fire riser room. Please revise the plans to include this room and the required illumination. [Ref. IBC 2018 Sec. 902.1.4]

2. Please indicate an exit sign in the area of door 101B that clearly indicates the direction of egress travel through that door. [Ref. IBC 2018 Sec.1013.1]


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
07/24/2025 Commercial Mechanical Standard REQUIRES RESUBMIT July 11, 2025
1st Review

Intertech Architectural Interiors
Attn: Maria Oldham
6089 E. Grant Road
Tucson, Arizona 85712

Re: QUALITY OF LIFE MEDICAL AND RESEARCH CENTER
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0625-01285
Stantec Project Number: 185215066
Stantec File Number: TUC-25-075

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B V-B 10,950 73 Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

1. The individual space square footage and the building area square footage are conflicting. The actual building area indicates 10,500 square feet while the individual space area is indicated as 10,950 square feet.

STRUCTURAL COMMENTS

There are no comments.


MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

General

1. The electrical sheets are missing the fire riser room. Please revise the plans to include this room and the required illumination. [Ref. IBC 2018 Sec. 902.1.4]

2. Please indicate an exit sign in the area of door 101B that clearly indicates the direction of egress travel through that door. [Ref. IBC 2018 Sec.1013.1]


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
07/24/2025 Commercial Plumbing Standard REQUIRES RESUBMIT July 11, 2025
1st Review

Intertech Architectural Interiors
Attn: Maria Oldham
6089 E. Grant Road
Tucson, Arizona 85712

Re: QUALITY OF LIFE MEDICAL AND RESEARCH CENTER
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0625-01285
Stantec Project Number: 185215066
Stantec File Number: TUC-25-075

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B V-B 10,950 73 Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

1. The individual space square footage and the building area square footage are conflicting. The actual building area indicates 10,500 square feet while the individual space area is indicated as 10,950 square feet.

STRUCTURAL COMMENTS

There are no comments.


MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

General

1. The electrical sheets are missing the fire riser room. Please revise the plans to include this room and the required illumination. [Ref. IBC 2018 Sec. 902.1.4]

2. Please indicate an exit sign in the area of door 101B that clearly indicates the direction of egress travel through that door. [Ref. IBC 2018 Sec.1013.1]


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
07/25/2025 Fire New Construction Standard REVIEW COMPLETED
07/07/2025 PDSD Application Completeness Express REVIEW COMPLETED