Permit Number: TC-COM-0625-01285
Parcel: 134234150

Review Status: Requires Resubmit

Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1

Permit Number - TC-COM-0625-01285
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/09/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/09/2025 Air Balancing/Commissioning Report (Deferred Submittal) Express REQUIRES RESUBMIT The submitted air balance report shows that RTU-9 is delivering only 83% of the required total air flowrate and less than 75% of the design air flowrate to the meeting rooms 123 and 124. Submit the report to the engineer for evaluation and resolution of the issue. Submit a revised air balance report once the problem has been resolved.
12/08/2025 PDSD Application Completeness Express REVIEW COMPLETED