Permit Number: TC-COM-0625-01285
Parcel: 134234150

Review Status: Requires Resubmit

Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.2

Permit Number - TC-COM-0625-01285
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/12/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/12/2025 Air Balancing/Commissioning Report (Deferred Submittal) Express REQUIRES RESUBMIT Submit an addendum to the air balance report showing the corrected air flow rates for the RTU-9 system along with the statement from the engineer accepting the current situation. [Initial comment: The submitted air balance report shows that RTU-9 is delivering only 83% of the required total air flowrate and less than 75% of the design air flowrate to the meeting rooms 123 and 124. Submit the report to the engineer for evaluation and resolution of the issue. Submit a revised air balance report once the problem has been resolved.]
12/10/2025 PDSD Application Completeness Express REVIEW COMPLETED