Permit Number: TC-COM-0625-01282
Parcel: 11012094F

Address:
5301 E GRANT RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0625-01282
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/28/2025 Commercial Mechanical Standard NOT REQUIRED
07/09/2025 Site Engineering Standard NOT REQUIRED
07/25/2025 Site Zoning Standard NOT REQUIRED
07/28/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/23/2025 Addressing Validation REQUIRES RESUBMIT Please identify the building number for the Material Management Building and include the building number in the title block of the construction documents
07/23/2025 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
1. Sheet g1: Please provide a detailed description of the work involved in this permit’s scope. IBC 105.3
2. Sheet g1: Please explain why structural steel is indicated as a separate permit. IBC 107.2.1
Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
07/17/2025 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0625-01282 (5301 E GRANT RD TUCSON, AZ 85712)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans, design, and calculations, sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304, 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/checklists/commercial_submittal_requirements_july2023.pdf
2. Provided plans must include all required repair work and other unpermitted work noted in the Job scope letter.

3. Provide an electrical plan showing any/all electrical work. Include an electrical floor or site plan showing the location of all new electrical work and equiptment.
Plans shall include, but may not be limited to items below:
4. Show all wiring methods in detail for all new or modified branch circuit conductors and feeders. Conductor type and conduit size/type. Note wet use requirements. NEC arts;300 and 408.4.
5. Provide new and updated panel schedules, showing the circuits that are being modified, added or removed. NEC arts;300 and 408.4.
6. Designate the circuit number, that corresponds to the panel schedule, at the location of each new or modified light fixture, receptacle, and equipment disconnect switch, NEC arts;300 and 408.4.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
07/07/2025 PDSD Application Completeness Express REVIEW COMPLETED