Permit Number: TC-COM-0625-01272
Parcel: 10603100C

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0625-01272
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/17/2025 Water - PDSD APPROVED
07/15/2025 Site Engineering NOT REQUIRED
07/29/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/29/2025 Commercial Building REQUIRES RESUBMIT July 8, 2025
1st Review

CMA, LLC.
Attn: Chuck Meyer
11598 W. Rock Village Street
Marana, Arizona 85658

Re: MEZO SMOKE SHOP
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0625-01272
Stantec Project Number: 185215066
Stantec File Number: TUC-25-074

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
M V-B 1,641 11 No No
Separate Permits: None.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

Sheet X1

1. The common path of egress maximum distance of 75’ appears to be exceeded when measured from the most remote point of the retail area. [Ref. IBC 2018 Sec. 1006.2.1] {Please note: The distance is considered a common path of travel due to the one exit in this space. The exit in the back of the tenant space cannot be utilized because egress through storage rooms is not permitted per IBC 2018 Sec. 1016.2.}


Sheet A1

1. The floor plans of the MEP portion of the plan-set appear to have a second exit door in the retail area on the east wall but this door is not located on the architectural floor plan. Please clarify and revise.

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

Sheet E2.0

1. The electrical feeder schedule on this sheet indicates that the circuit for the water heater will be located in Panel L21 which is in the adjacent tenant suite. The occupant of this suite must have access to overcurrent protection of the water heater. Please revise this to be located in Panel L20 of this tenant suite. [Ref. NEC 2018 Art. 240.24 (B)]


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
07/29/2025 Commercial Electrical REQUIRES RESUBMIT July 8, 2025
1st Review

CMA, LLC.
Attn: Chuck Meyer
11598 W. Rock Village Street
Marana, Arizona 85658

Re: MEZO SMOKE SHOP
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0625-01272
Stantec Project Number: 185215066
Stantec File Number: TUC-25-074

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
M V-B 1,641 11 No No
Separate Permits: None.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

Sheet X1

1. The common path of egress maximum distance of 75’ appears to be exceeded when measured from the most remote point of the retail area. [Ref. IBC 2018 Sec. 1006.2.1] {Please note: The distance is considered a common path of travel due to the one exit in this space. The exit in the back of the tenant space cannot be utilized because egress through storage rooms is not permitted per IBC 2018 Sec. 1016.2.}


Sheet A1

1. The floor plans of the MEP portion of the plan-set appear to have a second exit door in the retail area on the east wall but this door is not located on the architectural floor plan. Please clarify and revise.

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

Sheet E2.0

1. The electrical feeder schedule on this sheet indicates that the circuit for the water heater will be located in Panel L21 which is in the adjacent tenant suite. The occupant of this suite must have access to overcurrent protection of the water heater. Please revise this to be located in Panel L20 of this tenant suite. [Ref. NEC 2018 Art. 240.24 (B)]


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
07/29/2025 Commercial Mechanical REQUIRES RESUBMIT July 8, 2025
1st Review

CMA, LLC.
Attn: Chuck Meyer
11598 W. Rock Village Street
Marana, Arizona 85658

Re: MEZO SMOKE SHOP
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0625-01272
Stantec Project Number: 185215066
Stantec File Number: TUC-25-074

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
M V-B 1,641 11 No No
Separate Permits: None.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

Sheet X1

1. The common path of egress maximum distance of 75’ appears to be exceeded when measured from the most remote point of the retail area. [Ref. IBC 2018 Sec. 1006.2.1] {Please note: The distance is considered a common path of travel due to the one exit in this space. The exit in the back of the tenant space cannot be utilized because egress through storage rooms is not permitted per IBC 2018 Sec. 1016.2.}


Sheet A1

1. The floor plans of the MEP portion of the plan-set appear to have a second exit door in the retail area on the east wall but this door is not located on the architectural floor plan. Please clarify and revise.

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

Sheet E2.0

1. The electrical feeder schedule on this sheet indicates that the circuit for the water heater will be located in Panel L21 which is in the adjacent tenant suite. The occupant of this suite must have access to overcurrent protection of the water heater. Please revise this to be located in Panel L20 of this tenant suite. [Ref. NEC 2018 Art. 240.24 (B)]


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
07/29/2025 Commercial Plumbing REQUIRES RESUBMIT July 8, 2025
1st Review

CMA, LLC.
Attn: Chuck Meyer
11598 W. Rock Village Street
Marana, Arizona 85658

Re: MEZO SMOKE SHOP
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0625-01272
Stantec Project Number: 185215066
Stantec File Number: TUC-25-074

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
M V-B 1,641 11 No No
Separate Permits: None.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

Sheet X1

1. The common path of egress maximum distance of 75’ appears to be exceeded when measured from the most remote point of the retail area. [Ref. IBC 2018 Sec. 1006.2.1] {Please note: The distance is considered a common path of travel due to the one exit in this space. The exit in the back of the tenant space cannot be utilized because egress through storage rooms is not permitted per IBC 2018 Sec. 1016.2.}


Sheet A1

1. The floor plans of the MEP portion of the plan-set appear to have a second exit door in the retail area on the east wall but this door is not located on the architectural floor plan. Please clarify and revise.

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

Sheet E2.0

1. The electrical feeder schedule on this sheet indicates that the circuit for the water heater will be located in Panel L21 which is in the adjacent tenant suite. The occupant of this suite must have access to overcurrent protection of the water heater. Please revise this to be located in Panel L20 of this tenant suite. [Ref. NEC 2018 Art. 240.24 (B)]


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
07/16/2025 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-COM-0625-01272
20 W FORT LOWELL RD. - C-2
Smoke Shop (1st Review)

TRANSMITTAL DATE: ‎July 16, 2025

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the C-2 zone (UDC 4.7.21). Smoke Shop is an approved use in the zone (UDC Table 4.8-4), subject to Use Specific Standard 4.9.9.H.

1. Clarify what is proposed. The description provided states “change of use to smoke shop”. If this is a change of use than clearly demonstrate how all requirements of UDC Use Specific Standard 4.9.9.H are met.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.