Permit Number: TC-COM-0625-01227
Parcel: 140398820

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0625-01227
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/23/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/18/2025 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.
1. Please review our Commercial Submittal Requirements at https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/checklists/commercial_submittal_requirements_july2023.pdf
2. We have received your structural calculations and metal building drawings; however please submit a complete set of plans in accordance with SECTION 107 of the 2018 IBC and the PDSD Building Plan Requirements, a complete set of fully dimensioned plans demonstrating the full scope of work shall be provided. All plans must be sealed and signed by an Architect or Engineer registered in the State of Arizona. Note. The term ‘building plans’ may refer to structural, electrical, plumbing, or any other trade regulated by the associated suite of codes adopted by the City of Tucson.
3. Here is an excerpt from the Commercial Submittal Requirements these plans will have to be prepared by an Architect or Engineer as described above. IBC 107.2.1
Building Plan General Requirements:
• Cover Sheets
General Project information including address, location map and square footage. A complete Code Analysis should also be present detailing the type of construction, occupancy classification(s), occupancy loads, exiting requirements, fire sprinklers and fire alarms. Cover sheet must include a legend of symbols and abbreviations used throughout the plan set.
Architectural Requirements:
• Site Plan
A fully dimensioned site plan (not an aerial photograph) shall show project address including suite numbers and legal description. All easements with dimensions, lot area, north arrow, and scale. Location of all property lines, structure to property line setback dimensions (existing and proposed), proposed and existing utility meters, public sewer connections, sump pumps, back flow devices, and fire hydrant locations. Please provide street names for all adjacent streets, a fully dimensioned parking plan including tabulation of existing, proposed and required parking spaces. Locations of all buildings/structures on adjacent property within 10 feet of property line, including location and dimensions of all walkways and driveways related to ADA considerations. Submitted plans must be in compliance with the approved entitlements for the project and any conditions of approval.
This work is generally completed by an Architect.
Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
07/20/2025 Fire New Construction Standard REQUIRES RESUBMIT -Resolve all building comments. Need a complete set of plans to conduct a full review.
john.vincent@tucsonaz.gov
5203495581
07/23/2025 Site Engineering Standard REQUIRES RESUBMIT Permit: TC-COM-0625-01227
Location: 4801 E LOS REALES RD
Review Date: 7/23/2025
Site Engineering Comments:
1. This permit calls for a new proposed building and will require a site plan (Development Package) per UDC Article 3.3.3.G.2.c . Until the DP is reviewed and approved by all reviewing agencies, site engineering will be unable to review and approve the associated commercial building permit TC-COM-0625-01227.

If you have any questions or concerns, please contact
Marco Contreras
Marco.contreras@tucsonaz.gov
07/21/2025 Site Zoning Standard REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-COM-0625-01227
4801 E LOS REALES RD. – R-3
Metal Building (1st Review)

TRANSMITTAL DATE: July 21, 2025

Resubmit revised drawings with a detailed response letter stating how all Zoning Review Section comments were addressed.

This site is located in the R-3 zone (UDC 4.7.12). Use is unknown.

1. As a new building is proposed per UDC Article 3.3.3.G.2.c A site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A Development Package (DP) meeting the requirements of Administrative Manual (AM) 2-06 must be submitted and approved prior to approval of this building plan. The Administrative Manual can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes-and-Plans/Zoning-Code#section-1.

The Unified Development Code (UDC) can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Zoning-Code.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
06/27/2025 PDSD Application Completeness Express REVIEW COMPLETED