Permit Number: TC-COM-0625-01201
Parcel: 10818003B

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0625-01201
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/10/2025 Commercial Building APPROVED
06/30/2025 Commercial Electrical APPROVED
07/10/2025 Site Zoning APPROVED
07/10/2025 Water - PDSD APPROVED
06/26/2025 Site Engineering NOT REQUIRED
07/10/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/10/2025 Commercial Mechanical REQUIRES RESUBMIT Provide calculations to verify that adequate ventilation will be provided for the occupied spaces. Reference: Section 403.3.1.1, IMC 2018.
07/10/2025 Commercial Plumbing REQUIRES RESUBMIT Provide a detail of the water heater installation, showing how the recirculation system has been added or modified to serve the new sinks. Reference: Sections 503.1, 504, 606.1, 607.2, and 607.3 IPC 2018.
07/08/2025 Fire New Construction REVIEW COMPLETED
06/26/2025 PDSD Application Completeness Express REVIEW COMPLETED