Permit Review Detail
Review Status: Approved
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0625-01194
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Approved
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/09/2025 | Commercial Building Standard | APPROVED | 1. Sheet 0.1 Show distances to both exits. 2. Sheet A2.1 Show required dimension. 3. Sheet A2.1 Provide dimension for hall. 4. Sheet A2.1 Provide push side clearance min 12". 5. Sheet A2.1 Show required Clear Floor Space ICC A117.1 6. Sheet A2.1 Show accessible path of travel to parking and the Public Way. 7. Sheet FS1.0 Fire plan is not part of this review. Verify the AHJ. 8. Sheet E0.0 Fire Alarm not part of this review 9. Sheet E2.1F Fire Alarm Plan not included in this review. |
||
| 07/09/2025 | Commercial Electrical Standard | APPROVED | 1. Sheet E5.0 Identify amperage, voltage and wires. 2. Sheet E5.0 Panel A identify new conduit and wire sizes. |
||
| 07/09/2025 | Commercial Mechanical Standard | APPROVED | 1. Sheet M4.0 Show location of outside unit and where the freon lines are exiting the building along with protection of these lines. Show Electrical Supply lines to these units. | ||
| 07/09/2025 | Commercial Plumbing Standard | APPROVED | 1. Sheet P1.1 Provide detail for slab repair. 2. Sheet P2.1 Show where water heater T&P will discharge. Verify the location and height of discharge. |
||
| 07/07/2025 | Outdoor Lighting Standard | APPROVED | |||
| 07/17/2025 | Site Zoning Standard | APPROVED | |||
| 07/21/2025 | Water - PDSD Standard | APPROVED | |||
| 07/02/2025 | Site Engineering Standard | NOT REQUIRED | |||
| 07/21/2025 | Bldg Permits - Post Review Express | REVIEW COMPLETED | |||
| 07/17/2025 | Fire New Construction Standard | REVIEW COMPLETED | |||
| 06/26/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |