Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0625-01179
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/11/2025 | Site Zoning Standard | APPROVED | |||
| 07/14/2025 | Water - PDSD Standard | APPROVED | |||
| 06/30/2025 | Outdoor Lighting Standard | NOT REQUIRED | No modifications to the outdoor lighting | ||
| 06/26/2025 | Site Engineering Standard | NOT REQUIRED | |||
| 07/14/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/09/2025 | Commercial Building Standard | REQUIRES RESUBMIT | July 7, 2025 1st Review CMA, LLC Attn: Chuck Meyer 7623 E. Fair Meadows Loop Tucson, Arizona 85756 Re: ROLLIN SMOKE BBQ TENANT IMPROVEMENT City of Tucson Permit Number: TC-COM-0625-01179 Stantec Project Number: 185215066 Stantec File Number: TUC-25-072 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms A-2 V-B 6,000 215 Yes No Separate Permits: Automatic fire sprinklers, kitchen hood suppression system, and signage. Deferred Submittals: None. Special Inspections: Epoxy and expansion anchors, field welding, and masonry. ARCHITECTURAL COMMENTS General 1. Please provide proof that this project has been submitted to the Pima County Health Department for permitting. Make sure to incorporate any of their comments into any future submittals. 2. Please indicate that the automatic fire sprinkler system [2018 IBC Sec. 903], and kitchen hood suppression system [2018 IBC Sec. 904.12] are to be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal). 3. Note on the cover of the drawings that special inspection is required for epoxy and expansion anchors, field welding, and masonry. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form. Sheet X1 1. The code analysis indicates that this building does not have an automatic sprinkler system. Per 2018 IBC Sec. 903.2.1.2, an automatic sprinkler system is required in a Group A-2 Occupancy when the building area exceeds 5,000 square feet or if the occupant load is 100 or more people; this building fits both requirements. An automatic sprinkler system will be required. STRUCTURAL COMMENTS There are no comments. MECHANICAL COMMENTS There are no comments. PLUMBING COMMENTS Sheet P2 1. Adding up the cubic feet per hour of the listed gas fed equipment there appears to be 791 CFH total gas demand; however the total gas demand listed on the plans is 1,386 CFH. There are 5 mechanical units and a water heater that each requires gas, but the gas demand is not listed for these pieces of equipment. Please clarify this information on the plans. ELECTRICAL COMMENTS There are no comments. Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Joel Svoboda, RA Senior Associate 520-545-7415 joel.svoboda@stantec.com |
||
| 07/09/2025 | Commercial Electrical Standard | REQUIRES RESUBMIT | July 7, 2025 1st Review CMA, LLC Attn: Chuck Meyer 7623 E. Fair Meadows Loop Tucson, Arizona 85756 Re: ROLLIN SMOKE BBQ TENANT IMPROVEMENT City of Tucson Permit Number: TC-COM-0625-01179 Stantec Project Number: 185215066 Stantec File Number: TUC-25-072 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms A-2 V-B 6,000 215 Yes No Separate Permits: Automatic fire sprinklers, kitchen hood suppression system, and signage. Deferred Submittals: None. Special Inspections: Epoxy and expansion anchors, field welding, and masonry. ARCHITECTURAL COMMENTS General 1. Please provide proof that this project has been submitted to the Pima County Health Department for permitting. Make sure to incorporate any of their comments into any future submittals. 2. Please indicate that the automatic fire sprinkler system [2018 IBC Sec. 903], and kitchen hood suppression system [2018 IBC Sec. 904.12] are to be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal). 3. Note on the cover of the drawings that special inspection is required for epoxy and expansion anchors, field welding, and masonry. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form. Sheet X1 1. The code analysis indicates that this building does not have an automatic sprinkler system. Per 2018 IBC Sec. 903.2.1.2, an automatic sprinkler system is required in a Group A-2 Occupancy when the building area exceeds 5,000 square feet or if the occupant load is 100 or more people; this building fits both requirements. An automatic sprinkler system will be required. STRUCTURAL COMMENTS There are no comments. MECHANICAL COMMENTS There are no comments. PLUMBING COMMENTS Sheet P2 1. Adding up the cubic feet per hour of the listed gas fed equipment there appears to be 791 CFH total gas demand; however the total gas demand listed on the plans is 1,386 CFH. There are 5 mechanical units and a water heater that each requires gas, but the gas demand is not listed for these pieces of equipment. Please clarify this information on the plans. ELECTRICAL COMMENTS There are no comments. Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Joel Svoboda, RA Senior Associate 520-545-7415 joel.svoboda@stantec.com |
||
| 07/09/2025 | Commercial Mechanical Standard | REQUIRES RESUBMIT | July 7, 2025 1st Review CMA, LLC Attn: Chuck Meyer 7623 E. Fair Meadows Loop Tucson, Arizona 85756 Re: ROLLIN SMOKE BBQ TENANT IMPROVEMENT City of Tucson Permit Number: TC-COM-0625-01179 Stantec Project Number: 185215066 Stantec File Number: TUC-25-072 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms A-2 V-B 6,000 215 Yes No Separate Permits: Automatic fire sprinklers, kitchen hood suppression system, and signage. Deferred Submittals: None. Special Inspections: Epoxy and expansion anchors, field welding, and masonry. ARCHITECTURAL COMMENTS General 1. Please provide proof that this project has been submitted to the Pima County Health Department for permitting. Make sure to incorporate any of their comments into any future submittals. 2. Please indicate that the automatic fire sprinkler system [2018 IBC Sec. 903], and kitchen hood suppression system [2018 IBC Sec. 904.12] are to be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal). 3. Note on the cover of the drawings that special inspection is required for epoxy and expansion anchors, field welding, and masonry. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form. Sheet X1 1. The code analysis indicates that this building does not have an automatic sprinkler system. Per 2018 IBC Sec. 903.2.1.2, an automatic sprinkler system is required in a Group A-2 Occupancy when the building area exceeds 5,000 square feet or if the occupant load is 100 or more people; this building fits both requirements. An automatic sprinkler system will be required. STRUCTURAL COMMENTS There are no comments. MECHANICAL COMMENTS There are no comments. PLUMBING COMMENTS Sheet P2 1. Adding up the cubic feet per hour of the listed gas fed equipment there appears to be 791 CFH total gas demand; however the total gas demand listed on the plans is 1,386 CFH. There are 5 mechanical units and a water heater that each requires gas, but the gas demand is not listed for these pieces of equipment. Please clarify this information on the plans. ELECTRICAL COMMENTS There are no comments. Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Joel Svoboda, RA Senior Associate 520-545-7415 joel.svoboda@stantec.com |
||
| 07/09/2025 | Commercial Plumbing Standard | REQUIRES RESUBMIT | July 7, 2025 1st Review CMA, LLC Attn: Chuck Meyer 7623 E. Fair Meadows Loop Tucson, Arizona 85756 Re: ROLLIN SMOKE BBQ TENANT IMPROVEMENT City of Tucson Permit Number: TC-COM-0625-01179 Stantec Project Number: 185215066 Stantec File Number: TUC-25-072 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms A-2 V-B 6,000 215 Yes No Separate Permits: Automatic fire sprinklers, kitchen hood suppression system, and signage. Deferred Submittals: None. Special Inspections: Epoxy and expansion anchors, field welding, and masonry. ARCHITECTURAL COMMENTS General 1. Please provide proof that this project has been submitted to the Pima County Health Department for permitting. Make sure to incorporate any of their comments into any future submittals. 2. Please indicate that the automatic fire sprinkler system [2018 IBC Sec. 903], and kitchen hood suppression system [2018 IBC Sec. 904.12] are to be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal). 3. Note on the cover of the drawings that special inspection is required for epoxy and expansion anchors, field welding, and masonry. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form. Sheet X1 1. The code analysis indicates that this building does not have an automatic sprinkler system. Per 2018 IBC Sec. 903.2.1.2, an automatic sprinkler system is required in a Group A-2 Occupancy when the building area exceeds 5,000 square feet or if the occupant load is 100 or more people; this building fits both requirements. An automatic sprinkler system will be required. STRUCTURAL COMMENTS There are no comments. MECHANICAL COMMENTS There are no comments. PLUMBING COMMENTS Sheet P2 1. Adding up the cubic feet per hour of the listed gas fed equipment there appears to be 791 CFH total gas demand; however the total gas demand listed on the plans is 1,386 CFH. There are 5 mechanical units and a water heater that each requires gas, but the gas demand is not listed for these pieces of equipment. Please clarify this information on the plans. ELECTRICAL COMMENTS There are no comments. Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Joel Svoboda, RA Senior Associate 520-545-7415 joel.svoboda@stantec.com |
||
| 07/14/2025 | Fire New Construction Standard | REQUIRES RESUBMIT | -Resolve all building comments. -Consider using the IEBC to determine level of alteration and whether or not fire protection systems will be required. -Your listed square footage presents a problem. 5000 is the threshold for fire sprinklers now and in the past when the original CofO was issued. The previous CofO you provided has a square footage under 5k. Your current analysis shows a square footage over 5k. Please call/email to discuss. john.vincent@tucsonaz.gov 5203495581 |
||
| 06/20/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |