Permit Number: TC-COM-0625-01179
Parcel: 140122150

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0625-01179
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/11/2025 Site Zoning Standard APPROVED
07/14/2025 Water - PDSD Standard APPROVED
06/30/2025 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting
06/26/2025 Site Engineering Standard NOT REQUIRED
07/14/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/09/2025 Commercial Building Standard REQUIRES RESUBMIT July 7, 2025
1st Review

CMA, LLC
Attn: Chuck Meyer
7623 E. Fair Meadows Loop
Tucson, Arizona 85756

Re: ROLLIN SMOKE BBQ
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0625-01179
Stantec Project Number: 185215066
Stantec File Number: TUC-25-072

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
A-2 V-B 6,000 215 Yes No
Separate Permits: Automatic fire sprinklers, kitchen hood suppression system, and signage.
Deferred Submittals: None.
Special Inspections: Epoxy and expansion anchors, field welding, and masonry.

ARCHITECTURAL COMMENTS

General

1. Please provide proof that this project has been submitted to the Pima County Health Department for permitting. Make sure to incorporate any of their comments into any future submittals.

2. Please indicate that the automatic fire sprinkler system [2018 IBC Sec. 903], and kitchen hood suppression system [2018 IBC Sec. 904.12] are to be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal).
3. Note on the cover of the drawings that special inspection is required for epoxy and expansion anchors, field welding, and masonry. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form.

Sheet X1

1. The code analysis indicates that this building does not have an automatic sprinkler system. Per 2018 IBC Sec. 903.2.1.2, an automatic sprinkler system is required in a Group A-2 Occupancy when the building area exceeds 5,000 square feet or if the occupant load is 100 or more people; this building fits both requirements. An automatic sprinkler system will be required.

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

Sheet P2

1. Adding up the cubic feet per hour of the listed gas fed equipment there appears to be 791 CFH total gas demand; however the total gas demand listed on the plans is 1,386 CFH. There are 5 mechanical units and a water heater that each requires gas, but the gas demand is not listed for these pieces of equipment. Please clarify this information on the plans.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Joel Svoboda, RA
Senior Associate
520-545-7415
joel.svoboda@stantec.com
07/09/2025 Commercial Electrical Standard REQUIRES RESUBMIT July 7, 2025
1st Review

CMA, LLC
Attn: Chuck Meyer
7623 E. Fair Meadows Loop
Tucson, Arizona 85756

Re: ROLLIN SMOKE BBQ
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0625-01179
Stantec Project Number: 185215066
Stantec File Number: TUC-25-072

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
A-2 V-B 6,000 215 Yes No
Separate Permits: Automatic fire sprinklers, kitchen hood suppression system, and signage.
Deferred Submittals: None.
Special Inspections: Epoxy and expansion anchors, field welding, and masonry.

ARCHITECTURAL COMMENTS

General

1. Please provide proof that this project has been submitted to the Pima County Health Department for permitting. Make sure to incorporate any of their comments into any future submittals.

2. Please indicate that the automatic fire sprinkler system [2018 IBC Sec. 903], and kitchen hood suppression system [2018 IBC Sec. 904.12] are to be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal).
3. Note on the cover of the drawings that special inspection is required for epoxy and expansion anchors, field welding, and masonry. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form.

Sheet X1

1. The code analysis indicates that this building does not have an automatic sprinkler system. Per 2018 IBC Sec. 903.2.1.2, an automatic sprinkler system is required in a Group A-2 Occupancy when the building area exceeds 5,000 square feet or if the occupant load is 100 or more people; this building fits both requirements. An automatic sprinkler system will be required.

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

Sheet P2

1. Adding up the cubic feet per hour of the listed gas fed equipment there appears to be 791 CFH total gas demand; however the total gas demand listed on the plans is 1,386 CFH. There are 5 mechanical units and a water heater that each requires gas, but the gas demand is not listed for these pieces of equipment. Please clarify this information on the plans.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Joel Svoboda, RA
Senior Associate
520-545-7415
joel.svoboda@stantec.com
07/09/2025 Commercial Mechanical Standard REQUIRES RESUBMIT July 7, 2025
1st Review

CMA, LLC
Attn: Chuck Meyer
7623 E. Fair Meadows Loop
Tucson, Arizona 85756

Re: ROLLIN SMOKE BBQ
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0625-01179
Stantec Project Number: 185215066
Stantec File Number: TUC-25-072

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
A-2 V-B 6,000 215 Yes No
Separate Permits: Automatic fire sprinklers, kitchen hood suppression system, and signage.
Deferred Submittals: None.
Special Inspections: Epoxy and expansion anchors, field welding, and masonry.

ARCHITECTURAL COMMENTS

General

1. Please provide proof that this project has been submitted to the Pima County Health Department for permitting. Make sure to incorporate any of their comments into any future submittals.

2. Please indicate that the automatic fire sprinkler system [2018 IBC Sec. 903], and kitchen hood suppression system [2018 IBC Sec. 904.12] are to be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal).
3. Note on the cover of the drawings that special inspection is required for epoxy and expansion anchors, field welding, and masonry. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form.

Sheet X1

1. The code analysis indicates that this building does not have an automatic sprinkler system. Per 2018 IBC Sec. 903.2.1.2, an automatic sprinkler system is required in a Group A-2 Occupancy when the building area exceeds 5,000 square feet or if the occupant load is 100 or more people; this building fits both requirements. An automatic sprinkler system will be required.

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

Sheet P2

1. Adding up the cubic feet per hour of the listed gas fed equipment there appears to be 791 CFH total gas demand; however the total gas demand listed on the plans is 1,386 CFH. There are 5 mechanical units and a water heater that each requires gas, but the gas demand is not listed for these pieces of equipment. Please clarify this information on the plans.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Joel Svoboda, RA
Senior Associate
520-545-7415
joel.svoboda@stantec.com
07/09/2025 Commercial Plumbing Standard REQUIRES RESUBMIT July 7, 2025
1st Review

CMA, LLC
Attn: Chuck Meyer
7623 E. Fair Meadows Loop
Tucson, Arizona 85756

Re: ROLLIN SMOKE BBQ
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0625-01179
Stantec Project Number: 185215066
Stantec File Number: TUC-25-072

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
A-2 V-B 6,000 215 Yes No
Separate Permits: Automatic fire sprinklers, kitchen hood suppression system, and signage.
Deferred Submittals: None.
Special Inspections: Epoxy and expansion anchors, field welding, and masonry.

ARCHITECTURAL COMMENTS

General

1. Please provide proof that this project has been submitted to the Pima County Health Department for permitting. Make sure to incorporate any of their comments into any future submittals.

2. Please indicate that the automatic fire sprinkler system [2018 IBC Sec. 903], and kitchen hood suppression system [2018 IBC Sec. 904.12] are to be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal).
3. Note on the cover of the drawings that special inspection is required for epoxy and expansion anchors, field welding, and masonry. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form.

Sheet X1

1. The code analysis indicates that this building does not have an automatic sprinkler system. Per 2018 IBC Sec. 903.2.1.2, an automatic sprinkler system is required in a Group A-2 Occupancy when the building area exceeds 5,000 square feet or if the occupant load is 100 or more people; this building fits both requirements. An automatic sprinkler system will be required.

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

Sheet P2

1. Adding up the cubic feet per hour of the listed gas fed equipment there appears to be 791 CFH total gas demand; however the total gas demand listed on the plans is 1,386 CFH. There are 5 mechanical units and a water heater that each requires gas, but the gas demand is not listed for these pieces of equipment. Please clarify this information on the plans.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Joel Svoboda, RA
Senior Associate
520-545-7415
joel.svoboda@stantec.com
07/14/2025 Fire New Construction Standard REQUIRES RESUBMIT -Resolve all building comments.
-Consider using the IEBC to determine level of alteration and whether or not fire protection systems will be required.
-Your listed square footage presents a problem. 5000 is the threshold for fire sprinklers now and in the past when the original CofO was issued. The previous CofO you provided has a square footage under 5k. Your current analysis shows a square footage over 5k.
Please call/email to discuss.
john.vincent@tucsonaz.gov
5203495581
06/20/2025 PDSD Application Completeness Express REVIEW COMPLETED