Permit Number: TC-COM-0625-01175
Parcel: 11006134E

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.2

Permit Number - TC-COM-0625-01175
Review Name: COMMERCIAL REVIEW - LIMITED v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/14/2025 Commercial Electrical APPROVED
10/21/2025 Commercial Plumbing APPROVED
10/21/2025 Water - PDSD APPROVED
10/24/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/23/2025 Commercial Building REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
1. Please up date the code analysis to provide/or clarify the following information.
A. The square footage of the project looks like the entire space ic being renovated, not just 1164 SF
B. The total number of occupants for the floor is shown. IBC 107.2.3
C. The number of occupants is shown for every room and space. IBC 107.2.3
D. The occupant load factor and area are shown for every room and space. IBC 1004.5 For example Business areas typically use 150 occupant load factors. The waiting area would use an occupant load factor of 7 or 15.

2. Please provide an egress plan showing the paths of egress. IBC 107.2.3
A. The exit access travel distance is dimensioned with a clear start and stop point. IBC 1017.2
B. The common path of egress travel is dimensioned with a clear start and stop point. IBC 1006.2.1
Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
10/24/2025 Fire New Construction REQUIRES RESUBMIT Resolve building review comments.
Questions: patricia.shelton@tucsonaz.gov
10/08/2025 PDSD Application Completeness Express REVIEW COMPLETED