Permit Number: TC-COM-0625-01165
Parcel: 11918029L

Address:
1340 W AJO WY

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL REVISION v.1

Permit Number - TC-COM-0625-01165
Review Name: COMMERCIAL REVIEW - FULL REVISION v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/17/2025 Commercial Building Standard APPROVED
11/07/2025 Commercial Electrical Standard APPROVED
11/17/2025 Commercial Plumbing Standard APPROVED
11/17/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/17/2025 Commercial Mechanical Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0625-01165
ADDRESS/PARCEL: (1340 W AJO WY TUCSON, AZ 85713)
COMMENTS
1. Replacement of commercial AC units constitutes new work so the submittal will require a heating/cooling load calculation for the building to justify the capacities of the units being installed (Sections C403.3.1 and C403.2.2, IECC 2018). The units themselves will also have to comply with Sections C403.3.2, C403.4 and C403.5, IECC 2018 for efficiency, controls, and economizers. While ventilation calculations are not required, a test and air balance report is required. Reference: Section C503.4, IECC 2018.
2. Also, please provide the weight of the existing (removed) HVAC units
11/12/2025 Fire New Construction Standard REVIEW COMPLETED
10/28/2025 PDSD Application Completeness Express REVIEW COMPLETED