Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL REVISION v.1
Permit Number - TC-COM-0625-01165
Review Name: COMMERCIAL REVIEW - FULL REVISION v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/17/2025 | Commercial Building Standard | APPROVED | |||
| 11/07/2025 | Commercial Electrical Standard | APPROVED | |||
| 11/17/2025 | Commercial Plumbing Standard | APPROVED | |||
| 11/17/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 11/17/2025 | Commercial Mechanical Standard | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-0625-01165 ADDRESS/PARCEL: (1340 W AJO WY TUCSON, AZ 85713) COMMENTS 1. Replacement of commercial AC units constitutes new work so the submittal will require a heating/cooling load calculation for the building to justify the capacities of the units being installed (Sections C403.3.1 and C403.2.2, IECC 2018). The units themselves will also have to comply with Sections C403.3.2, C403.4 and C403.5, IECC 2018 for efficiency, controls, and economizers. While ventilation calculations are not required, a test and air balance report is required. Reference: Section C503.4, IECC 2018. 2. Also, please provide the weight of the existing (removed) HVAC units |
||