Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0625-01165
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/10/2025 | Site Zoning Standard | APPROVED | |||
| 07/10/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/08/2025 | Commercial Building Standard | REQUIRES RESUBMIT | Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed. 1. Please amend the plans so the number of occupants (70) on sheet T1.0 under Occupancy & Plumbing Calculations matches the number of occupants (82) on sheet T2.0. IBC 107.2.1 2. Please indicate the height of the racking in the storage area of the building. IBC 107.2.1. A. The racking can be treated as a deferred submittal as nonfixed and movable fixtures, cases, racks, counters and partitions over 5 feet 9 inches in height require a permit. Racking less than 8 feet: For racking more than 5’-9” but less than 8 feet in height, stamped structural plans are not required. Instead, submit the manufacturer’s installation details and specifications. Racking over 8 feet will require engineered design and anchorage details Please contact me if you have any questions about these comments. Mark Masek Plans Examiner – Building Safety Planning and Development Services | City of Tucson main 520.837.4994 email mark.masek@tucsonaz.gov |
||
| 06/27/2025 | Commercial Electrical Standard | REQUIRES RESUBMIT | Commercial Electrical Review TC-COM-0625-01165 (1340 W AJO WY TUCSON, AZ 85713) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC). 1. Provide Fault Current Analysis and show new equipment AIC rating sufficient to withstand the calculated Fault Current. Provide Available Fault Current calculations from TEP transformers to all new equipment, 2017 NEC 110.24. 2. Show new Panels and other new equipment with AIC ratings greater than or equal to the Available Fault Currents calculated, 2017 NEC 110.10. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 07/10/2025 | Fire New Construction Standard | REQUIRES RESUBMIT | -Resolve all building comments. -Make correction to applicable codes, sheet T1.0. COT/TFD has adopted 2024 IFC. John.vincent@tucsonaz.gov 5203495581 |
||
| 06/18/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |