Permit Number: TC-COM-0625-01115
Parcel: 12404032B

Address:
1443 E 1ST ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0625-01115
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/27/2025 Site Zoning Standard APPROVED
06/27/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/20/2025 Commercial Building Standard REQUIRES RESUBMIT 1. Sheet c0.01 Plans and index appears to be missing sheets within plans that are identified in plan notes. Doors (a104), Keynote 3.06 new single door between cafe & serving. Provide door data and hardware on plans. 2018IBC 107.2.1 (BM)
[ Ver. 2 ] [Edited By Bill McClellan]
2. Sheet a1.01 Keynote 3.07 identifies a new serving window opening in existing bearing wall. Provide framing / header data for review. Incomplete 2018 IBC 107.2.1 (BM)
3. Sheet a1.01 Keynote 3.08 identifies a new roll up window in wall. Wall is not identified as new from note 2.01 on demo plan. Clarify wall and window dimensions and height. Incomplete 2018 IBC 107.2.1 (BM)
4. Sheet a1. Provide window schedule on plans as identified per keynotes 3.07 & 3.082018 IBC 107.2.1 (BM)
[ Ver. 2 ] [Edited By Bill McClellan]
5. Sheet a1.02 keynote 3.16 is noted as double door, plan identifies window. Clarify on plans. 2018 IBC 107.2.1 (BM)
06/20/2025 Commercial Electrical Standard REQUIRES RESUBMIT
06/20/2025 Commercial Mechanical Standard REQUIRES RESUBMIT 1. Sheet M1.00 Plan identifies new electric double stack oven at hot line area next to existing hood. Clarify if new oven will require a Type 1 or II hood or if equipment meets 2018 IMC 507.2 exception or 507.3. Not clear on plans an no data provided for ovens.(BM)
06/20/2025 Commercial Plumbing Standard REQUIRES RESUBMIT Sheet c0.01 For questions in regards to plan review comments, please contact Bill McClellan by email at bmcclellan@willdan.com or cell (928)580-3179
06/10/2025 Fire New Construction Standard REVIEW COMPLETED
06/09/2025 PDSD Application Completeness Express REVIEW COMPLETED