Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-0625-01104
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/06/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/06/2025 | Commercial Electrical Standard | REQUIRES RESUBMIT | Commercial Electrical Review TC-COM-0625-01104 (3202 N 1ST AV TUCSON, AZ 85719) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC). >>> the previous comment was not addressed. 1. Incomplete Submittal – Please include a detailed construction plan along with any product specs that may be necessary to provide a commercial plan review. This is a commercial project, requiring all documents to be prepared, sealed, signed and dated by an Arizona registered design professional. https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/checklists/commercial_submittal_requirements_july2023.pdf >>> additional comments: 2. A letter is not construction plans that show the scope of work being completed. Provide an electrical plan showing any/all electrical work. Plans shall include (as necessary for scope of work), but may not be limited to items below: 3. Electrical demo plans. 4. Electrical floor plan that shows the location of all new or modified electrical work. 5. Provide electrical load calculations, for the Main Service Panel, Per NEC 220.40. 6. Show all wiring methods in detail for all new or modified branch circuit conductors and feeders for lights that were added. Conductor type and conduit size/type. Note wet use requirements. NEC arts;300 and 408.4. 7. Provide a panel schedules, showing the circuits that are being modified, added or removed or existing. NEC arts;300 and 408.4. Include panel bus rating and A.I.C. rating. IBC 107.1. 8. Designate the circuit number on the electrical plans, that corresponds to the panel schedule, at the location of each, new or modified light fixture, receptacle, and equipment disconnect switch, NEC arts;300 and 408.4. IBC 107.1. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 10/06/2025 | Outdoor Lighting Standard | REQUIRES RESUBMIT | Outdoor Lighting Review TC-COM-0625-01104 (3202 N 1ST AV TUCSON, AZ 85719) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC). Outdoor Lighting Review: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf 1. With any modifications, alterations, additions to the outdoor lighting are being made, Provide an outdoor site lighting plan that meets the requirements of OLC 104.2. Show/locate the different light sources on your site plan. Number the light fixtures on your lighting fixture table and use the same number on your site plan. 2. Show the developed area being used in your lumens calculations for max lumens. Typically the developed area of a commercial site is the entire parcel. 3. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 104.2.1, 401.2. Include all exterior fixtures on the property in the calculations. List shielded and unshielded lights in the calculation. >>> the calculating provided was for single family residential property. 4. Show lamps with a maximum of 3500K color temperature, OLC 402.1. 5. Provide manufacturer’s specification sheets, with the lumen and color temperature highlighted, showing the lights are full cut off and ratings. Additional comments may be forthcoming with the receipt of a complete plan set. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 10/06/2025 | PDSD Application Completeness Express | REVIEW COMPLETED | Site Plan Required |