Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-COM-0625-01093
Parcel: 140430010

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0625-01093
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/26/2025 Site Zoning Standard APPROVED
06/05/2025 Outdoor Lighting Standard NOT REQUIRED No modifications to the Outdoor Lighting.
06/20/2025 Site Engineering Standard NOT REQUIRED
06/26/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/20/2025 Commercial Building Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0625-01093
ADDRESS/PARCEL: (1840 E VALENCIA RD TUCSON, AZ 85706)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval.

COMMENTS:
1. Uplift Calculation Information to be submitted based on the 115 MPH 3 second wind gust and the Roof Load Calculation showing the maximum allowable of 40 lbs per point load and maximum allowable of 4 lbs per square foot on roof. Allowance shall be provided for equipment weighing a maximum of 4 psf. The 4 psf allowance is applicable to conventional roofs (wood/steel deck and joist/beam or truss systems), exclusive of engineered metal buildings. Point loads not exceeding 45 lbs shall be provided a clear radius within which no other point load radiuses shall impinge. Uplift pressure to comply to the 2018 IBC 3111. These items are the responsibility of the Applicant and their Aizona registrant Structural Engineer.
2. Please resubmit.
If you have any questions about these comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976
06/09/2025 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0625-01093 (1840 E VALENCIA RD TUCSON, AZ 85706)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).


1. Show interconnection in compliance with NEC 705.32. Reference also NEC 230.95
705.32 Ground-Fault Protection. Where ground-fault protection is used, the output of an interactive system shall be connected to the supply side of the ground-fault protection. Exception: Connection shall be permitted to be made to the load side of ground-fault protection, if there is ground-fault protection for equipment from all ground-fault current sources.

2. Note or show compliance with NEC 705.22 item 1.
705.22 Disconnect Device. The disconnecting means for ungrounded conductors shall consist of a manual or power operated switch(es) or circuit breaker(s) that complies with the following: (1) Located where readily accessible

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
06/04/2025 Fire New Construction Standard REVIEW COMPLETED System shall comply with Section 1204 Solar photo voltaic systems of the 2024 IFC.
06/04/2025 PDSD Application Completeness Express REVIEW COMPLETED