Permit Number: TC-COM-0625-01092
Parcel: 119421830

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.2

Permit Number - TC-COM-0625-01092
Review Name: COMMERCIAL REVIEW - LIMITED v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/16/2025 Commercial Building APPROVED
06/17/2025 Commercial Mechanical APPROVED
06/17/2025 Commercial Plumbing APPROVED
06/20/2025 Site Zoning APPROVED
06/17/2025 Water - PDSD APPROVED
06/25/2025 Site Engineering NOT REQUIRED
06/25/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/05/2025 Commercial Electrical REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0625-01092 (1360 W IRVINGTON RD Unit:UNIT 180 TUCSON, AZ 85746)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. Show all wiring methods in detail for all new or modified branch circuit conductors and feeders. Conductor type and conduit size/type. Note wet use requirements. NEC arts;300 and 408.4.
2. Provide new and updated panel schedules, showing the circuits that are being modified, added or removed. NEC arts;300 and 408.4.
3. Designate the circuit number, that corresponds to the panel schedule, at the location of each new or modified light fixture, receptacle, and equipment disconnect switch or other outlet, NEC arts;300 and 408.4.
4. Provide electrical load calculations, for the Main Service Panel, Per NEC 220.40.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
06/05/2025 Fire New Construction REVIEW COMPLETED
06/04/2025 PDSD Application Completeness Express REVIEW COMPLETED