Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-0624-01273
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/20/2024 | Commercial Structural | APPROVED | |||
09/23/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
09/23/2024 | Commercial Mechanical | REQUIRES RESUBMIT | 1. Comment not resolved; the code section numbers shown are not from the 2018 IECC. [Initial comment: Revise the section references in the IECC Notes (sheet M2) to correspond to the Commercial Provisions of the 2018 IECC.] 2. Correct the arithmetic on the air balance schedule and coordinate the hood exhaust flow rate with the Exhaust Hood Calculations. [Initial comment: Provide air balancing data for the Type I hood, the makeup air unit, exhaust fans, and other sources of outside air to verify that the room pressure remains essentially neutral. Reference: Section 501.4, IMC 2018.] 3. Smoke detectors shall be located upstream of the filters. [Initial comment: Smoke detectors shall be installed in the return air duct, upstream of any outside air connections, for all air distribution systems moving than 2,000 CFM (See keynote 2, Sheet M2). Reference: Section 606.2.1, IMC 2018, as amended by the City of Tucson. |
||
09/23/2024 | Commercial Plumbing | REQUIRES RESUBMIT | The minimum gas pressure for the specified fryers is 7” H2O. Southwest Gas, the local gas utility, provides natural gas at 7” WG, 2 PSIG, and 5 PSIG. Appliances needing gas service at 7” WG or greater will require a gas meter that delivers at least 2 PSIG gas into a regulator located after the meter set. The total new demand, based on the gas isometric is 540 CFH, not 556 CFH. Reference: Section 402.1, IFGC 2018. [Initial comment: New gas-fired cooking appliances are scheduled for installation under the Type I hood. Show how the complete natural gas piping system will be modified. Provide a natural gas piping design, including the piping layout on a floor plan and a natural gas schematic showing the sizes, loads and developed lengths of the piping. Reference: Section 107.2.1, IBC 2018.] | ||
09/03/2024 | Historic | REQUIRES RESUBMIT | Pages A1 and A2 of the submitted plans still show the roll up door being removed and replaced with a solid wall. Please update the plans to accurately reflect the revised scope of work. | ||
08/23/2024 | PDSD Application Completeness | REVIEW COMPLETED |