Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0624-01256
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/25/2024 | Commercial Electrical | APPROVED | |||
| 08/02/2024 | Commercial Structural | APPROVED | |||
| 07/24/2024 | Site Zoning | APPROVED | |||
| 07/31/2024 | Commercial Mechanical | NOT REQUIRED | |||
| 07/31/2024 | Site Engineering | NOT REQUIRED | |||
| 08/02/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/31/2024 | Commercial Plumbing | REQUIRES RESUBMIT | Clarify the description of the proposed metering faucet operation. The description cites a 2.0 Gallon per cycle, a 12-second cycle, and a flowrate of 0.5 GPM. Faucets serving lavatories in all buildings other than R3 occupancies, individual units in R2 occupancies, or International Residential Code structures shall be automatic faucets dispensing a maximum of 0.25 gallons per cycle. The cycle time shall not be less than ten-seconds for accessibility. Reference: Section 419.6, IPC 2018 as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09. | ||
| 07/31/2024 | Fire New Construction | REVIEW COMPLETED | |||
| 06/26/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |