Permit Number: TC-COM-0624-01215
Parcel: 124050620

Review Status: Requires Resubmit

Review Details: RESTAMP - COMMERCIAL v.1

Permit Number - TC-COM-0624-01215
Review Name: RESTAMP - COMMERCIAL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/11/2025 Commercial Electrical Express APPROVED
02/12/2025 Commercial Mechanical Express APPROVED
02/12/2025 Site Engineering Express APPROVED
02/13/2025 Site Zoning Express APPROVED
02/13/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/12/2025 Commercial Plumbing Express REQUIRES RESUBMIT Drawing P-2 is not the same as the previously approved drawing. The submitted drawing shows incorrect connected gas loads or input ratings for each appliance. The AC units are scheduled with a gas input of 158.4 MBH but the Gas Diagram, A/P-2, shows a 150 MBH gas input for each unit and a total of 318 MBH and the Gas Meter Load shows a gas input of 159 MBH for each unit. Reference: Section 402.1, IFGC 2018.
02/11/2025 Fire New Construction Express REVIEW COMPLETED