Permit Number: TC-COM-0624-01214
Parcel: 12901035M

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0624-01214
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/24/2024 Site Zoning APPROVED
07/31/2024 Site Engineering NOT REQUIRED
08/02/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
07/25/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 The electrical plans are not sealed by an Arizona Registrant.

2 Ref; Plan sheet E-0-0. 2a. The GENERAL NOTES are not complete. See note #29.

2b. This multi-family building is categorized as commercial. Remove all references to the IRC and revise to the 2017 NEC.

3 Please identify all units associated with this remodel project on the electrical power and lighting plans.

4 Provide a detailed description of the scope of electrical work.

5 Please indicate what is proposed new electrical and what is existing to remain on all electrical power and lighting plans including power distribution from the electrical service equipment to and including the units.

6 Provide an electrical site plan showing the locations and identifying all service equipment and exterior lighting.

7 Provide complete compliance with the 2012 City of Tucson Outdoor Lighting Code. The cover plan sheet shows the project area at 3.37 Acres and the Outdoor Lumen calculations show 2 values for area, .10 Acres and .37 Acres. Please clarify and provide full compliance with the Outdoor Lighting Code. See Chapter 104 for plan submittal requirements and show all data required to verify compliance.

Be advised. Additional comments may be generated in the subsequent review due to insufficient information provided per this submittal.

Ref; 2018 IBC section 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements.
07/31/2024 Commercial Mechanical REQUIRES RESUBMIT Provide plans sealed by an Arizona Registrant that accurately reflect the proposed scope of work. Reference: Section 107.1, IBC 2018 and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304
07/31/2024 Commercial Plumbing REQUIRES RESUBMIT Provide plans sealed by an Arizona Registrant that accurately reflect the proposed scope of work. Reference: Section 107.1, IBC 2018 and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304
08/02/2024 Commercial Structural REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter to address each of the comments indicating how the Building Review comments were addressed. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.

Please amend plans to provide designer’s seal, signature, and date signed on all sheets. IBC 107.1
Please amend plans to provide a list that includes all the drawing sheets in this permit’s scope. IBC 107.2.1
Please amend plans to provide a detailed description of the work involved in this permit’s scope. IBC 105.3 Additionally, provide plans relevant to this project.


Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
07/31/2024 Fire New Construction REVIEW COMPLETED
06/26/2024 PDSD Application Completeness REVIEW COMPLETED Permit will be in review only for the address listed on the application, customer will need to submit a permit application for each unit affected by fire.