Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.4
Permit Number - TC-COM-0624-01208
Review Name: COMMERCIAL REVIEW - LIMITED v.4
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/30/2024 | Commercial Building | APPROVED | |||
10/31/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
10/31/2024 | Commercial Plumbing | REQUIRES RESUBMIT | Correct the Gas Demand Schedule to correspond to the revised gas distribution system. [Initial comment: Why is natural gas being supplied to a heat pump? Reference: Section 107.2.1, IBC 2018. ] | ||
10/17/2024 | PDSD Application Completeness | REVIEW COMPLETED |