Permit Number: TC-COM-0624-01208
Parcel: 117062910

Address:
434 E 9TH ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.3

Permit Number - TC-COM-0624-01208
Review Name: COMMERCIAL REVIEW - LIMITED v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/07/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
10/07/2024 Commercial Building REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter to address each of the comments indicating how the Building Review comments were addressed. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.
11. Sheet A1.1: Please amend plans to show how the requirements for the kitchen are in compliance with 2009 ICC A117.1 Section 804. This would include clear floor space, controls, heights, reach, etc. For example, show/specify an , clear floor space centered on each appliance 804.5, operable parts 804.5.2
Comment partially remains; Please amend plans to provide kitchen sink showing:
Front approach IBC - 1109.4, 2009 ICC A117.1 - 804.5.4.2
Knee and toe clearance 2009 ICC A117.1 – Section 306

Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
10/07/2024 Commercial Plumbing REQUIRES RESUBMIT 1. Revise the water heater detail to show the proper installation of a lead-free vacuum relief valve (i.e. the valve is to be located on a cold water supply line above the highest point of the tank of the water heater). Show that the installation of the water heater above the ceiling complies with the requirements of Sections 306.3 and 306.3.1, IFGC 2018. [Second comment: Comment not addressed.] [Initial comment: Identify the source of domestic hot water. If the water heater is being installed, provide a detail of the water heater installation, including the excess pressure relief, expansion tank, vacuum relief or other anti-siphon device, safety pan, and valves. Reference: Sections 503.1, 504, 606.1, 607.2, and 607.3, IPC 2018.]
2. The maximum distance between the hot water source and the termination for a public lavatory is 6” for a ¾” hot water supply, 24” for a ½” hot water supply. If a central water heater is to be used, a hot water recirculation system will be required. [Second comment: Comment not addressed.] The notes describing the hot water recirculation, the piping drawing, and the placement of a recirculation pump do not appear to result in a working hot water recirculation system. In addition, hot water recirculation systems are required to have controls that automatically turn off the recirculation pump when there is no hot water demand. Reference: Section C404.6.1, IECC 2018. [Initial comment: Verify that the distance from the hot water source to the hot water termination for the lavatories complies with the requirements of Section C404.5, IECC 2018.]
3. Why is natural gas being supplied to a heat pump? Reference: Section 107.2.1, IBC 2018.
09/24/2024 PDSD Application Completeness REVIEW COMPLETED