Review Status: Requires Resubmit

Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1

Permit Number - TC-COM-0624-01199
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/18/2024 Water Sterilization Report (Deferred Submittal) APPROVED
12/18/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
12/18/2024 Air Balancing/Commissioning Report (Deferred Submittal) REQUIRES RESUBMIT The mechanical design clearly shows outside air being supplied to each of the four air handlers but the air balance report does not show any outside air being supplied to the units. Correct this omission and resubmit the report. Reference: Section 403.3.1.5, IMC 2018, as amended by the City of Tucson.
12/18/2024 PDSD Application Completeness REVIEW COMPLETED