Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0624-01199
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/26/2024 | Commercial Plumbing | APPROVED | |||
08/05/2024 | Commercial Structural | APPROVED | |||
07/22/2024 | Site Zoning | APPROVED | |||
07/26/2024 | Water - PDSD | APPROVED | |||
07/29/2024 | Site Engineering | NOT REQUIRED | |||
08/05/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
07/24/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 Show the lighting branch circuits and panel assigned to the modified lighting in the lighting floor plans. 2 The panel schedules branch circuit descriptions are not acceptable. Revise to comply with NEC art 408.4. Ref; 2018 IBC section 107.2.1, 2017 NEC |
||
07/26/2024 | Commercial Mechanical | REQUIRES RESUBMIT | Revise the mechanical design as required to avoid using the corridors as return air ducts. Reference: Section 601.2, IMC 2018 | ||
07/30/2024 | Fire New Construction | REVIEW COMPLETED | |||
06/24/2024 | PDSD Application Completeness | REVIEW COMPLETED |