Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0624-01199
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/26/2024 Commercial Plumbing APPROVED
08/05/2024 Commercial Structural APPROVED
07/22/2024 Site Zoning APPROVED
07/26/2024 Water - PDSD APPROVED
07/29/2024 Site Engineering NOT REQUIRED
08/05/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
07/24/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 Show the lighting branch circuits and panel assigned to the modified lighting in the lighting floor plans.

2 The panel schedules branch circuit descriptions are not acceptable. Revise to comply with NEC art 408.4.



Ref; 2018 IBC section 107.2.1, 2017 NEC
07/26/2024 Commercial Mechanical REQUIRES RESUBMIT Revise the mechanical design as required to avoid using the corridors as return air ducts. Reference: Section 601.2, IMC 2018
07/30/2024 Fire New Construction REVIEW COMPLETED
06/24/2024 PDSD Application Completeness REVIEW COMPLETED