Permit Number: TC-COM-0624-01197
Parcel: 117042860

Address:
531 N 4TH AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.2

Permit Number - TC-COM-0624-01197
Review Name: COMMERCIAL REVIEW - LIMITED v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/15/2024 Commercial Building APPROVED
08/14/2024 Commercial Mechanical APPROVED
08/15/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
08/07/2024 Commercial Electrical REQUIRES RESUBMIT Please address the following electrical plan review comments. Also provide a written response.

The submitted lighting plan showing existing exterior under canopy string lighting only is not enough evidence that the lighting complies with the requirements of the Outdoor Lighting Code. Provide a copy(s) of the permitted and approved string lighting installation. The option is to provide the following;

Provide plans and evidence on the plans that the proposed exterior lighting on this parcel fully complies with the Outdoor Lighting Code. See section 104 for plan submittal requirements.

1. Provide site lighting plans with the following information on the plans;

(a) Provide a complete luminaire schedule.

(b) Full compliance with sections 104.2.1(1), (2), (3).

2 See table 401.1, Include parcel size, lighting area and option, and indicate this information in the lighting site plan.

3 402.1 (light source color temperature requirements, 3500K), shielding requirements, etc .

4 Provide calcs for total lumens allowed and total lumens proposed per acre for Full Cut Off and Unshielded per table 401.1. Must include existing to remain lighting.

5 Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2.

6 Specify any exceptions used.

7 Provide Curfew lighting controls If applicable Per section 403.

Be advised, the option to submit an appeal to the Building Official for a code variance is available through the PDSD online process.

Ref; 2017 NEC, 2012 Tucson/Pima County Outdoor Lighting Code (OLC), 2018 IBC sec 107.2.1.
07/30/2024 PDSD Application Completeness REVIEW COMPLETED