Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0624-01180
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/17/2025 | Site Zoning Standard | APPROVED | |||
| 04/18/2025 | Commercial Building Standard | NOT REQUIRED | |||
| 04/18/2025 | Site Engineering Standard | NOT REQUIRED | |||
| 04/18/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 04/03/2025 | Commercial Electrical Standard | REQUIRES RESUBMIT | Commercial Electrical Review TC-COM-0624-01180 (2613 E GRANT RD Unit:UNIT 1 TUCSON, AZ 85716) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC). 1. Clarify if this is a new service specific to unit 2 with a new riser. The original plans show a single main service entrance and a 200A panel feeding the two sub panels. 2. Provide a complete line diagram, NEC 110.2, 2018 IBC 107.1. Show the connection from the TEP power source each sub meter and sub panel. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 03/26/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |