04/17/2025 Site Zoning Standard APPROVED
04/18/2025 Commercial Building Standard NOT REQUIRED
04/18/2025 Site Engineering Standard NOT REQUIRED
04/18/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/03/2025 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0624-01180 (2613 E GRANT RD Unit:UNIT 1 TUCSON, AZ 85716)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. Clarify if this is a new service specific to unit 2 with a new riser. The original plans show a single main service entrance and a 200A panel feeding the two sub panels.
2. Provide a complete line diagram, NEC 110.2, 2018 IBC 107.1. Show the connection from the TEP power source each sub meter and sub panel.
Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov