Permit Number: TC-COM-0624-01171
Parcel: 11012007B

Address:
5151 E GRANT RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.4

Permit Number - TC-COM-0624-01171
Review Name: COMMERCIAL REVIEW - FULL v.4
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/18/2025 Commercial Mechanical APPROVED
06/23/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/23/2025 Commercial Structural REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Building Review comments were addressed. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
25. Sheet A1.0, Sheet ID601: The accessible 36” width appears to be interrupted by the 10” wide 42inch high Counter. Please adjust so a portion of the counter surface, 36 inches minimum in length and 36 inches maximum in height above the floor shall be provided.
COMMENT REMAINS AND IS EXPANDED: Sheet A1.0 shows a 30” high lower counter (code would allow 36” high) as accessible area with a code compliant length. Sheet ID601 shows a 36” high accessible counter, with a length less the minimum of 36”. Please coordinate both drawings so the same information is shown.
Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
06/18/2025 PDSD Application Completeness Express REVIEW COMPLETED